IOM VLH VLC 704 1204

Page 49
English
VLH/VLC HSE STD 704 804 904 1004 1104 1204
Rated voltage V/ph/Hz 400 (±10%) /3/50
Max. absorbed power kW 86,4 95,7 109,8 120,8 138,6 156,4
Rated current A 114,52 116,76 137,78 154 174,5 195
Max. current FLA A 155,8 161,2 190 214 247,4 280,8
Max. start-up current LRA A 359,1 364,5 428,3 452,3 492 525,4
External fuses A 250 250 250 250 315 315
Max. cable section (*) mm
2
3x120 3x120 3x120 3x120 3x185 3x185
Exchanger resistance
Rated voltage V/ph/Hz 230/ (± 10%)/1/50
Max. absorbed power W 130
VLH/VLC HSE L 704 804 904 1004 1104 1204
Rated voltage V/ph/Hz 400 (±10%) /3/50
Max. absorbed power kW 86,4 95,7 109,8 120,8 138,6 156,4
Rated current A 114,52 116,76 137,78 154 174,5 195
Max. current FLA A 155,8 161,2 190 214 247,4 280,8
Max. start-up current LRA A 359,1 364,5 428,3 452,3 492 525,4
External fuses A 250 250 250 250 315 315
Max. cable section (*) mm
2
3x120 3x120 3x120 3x120 3x185 3x185
Exchanger resistance
Rated voltage V/ph/Hz 230/ (± 10%)/1/50
Max. absorbed power W 130
VLH/VLC HSE S 704 804 904 1004 1104 1204
Rated voltage V/ph/Hz 400 (±10%) /3/50
Max. absorbed power kW 86,4 95,7 109,8 120,8 138,6 156,4
Rated current A 114,52 116,76 137,78 154 174,5 195
Max. current FLA A 155,8 161,2 190 214 247,4 280,8
Max. start-up current LRA A 359,1 364,5 428,3 452,3 492 525,4
External fuses A 250 250 250 250 315 315
Max. cable section (*) mm
2
3x120 3x120 3x120 3x120 3x185 3x185
Exchanger resistance
Rated voltage V/ph/Hz 230/ (± 10%)/1/50
Max. absorbed power W 130
Technical data
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working
temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.