TS VLS H C 604 1204 GB 0617
Table Of Contents
- Tender Specification
- USERIESU: VLS / VLH / VLC 604-1204
- UTYPEU: Air cooled water chiller, heat pump and condensing unit
- UTECHNOLOGYU: multi-scroll compressors, R410A refrigerant
- UCAPACITY RANGEU:
- Cooling ( 153-307 [kW]
- Heating ( 170-337 [kW]
- 1 General description
- 2 Key points
- 3 Cabinet
- 4 Compressors
- 5 Evaporator
- 6 Condenser
- 7 Condenser fans
- 8 Refrigerant circuit
- 9 Control panel
- 10 Safety and control devices
- 11 Optional hydro kits
- 12 Factory installed options
- 13 Field installed accessories
- 14 Conformity with standards
Tender Specification
VLS / VLH / VLC 604-1204
2 Key points
• High seasonal performances ESEER up to 4.1
• Common configuration for the different versions Easy upgrade of the units
in stock or on field
• Electronic expansion device Excellent control of superheating for the best
performance at full and partial load and for a safe operation
• Microchannel coils for VLS version Significant reduction on refrigerant
charge and operating weight
• Compressors box Remarkable sound reduction even for the basic noise
version
• Control platform Modular architecture, compressor envelope integration,
corrective actions in border line areas, easy-friendly user interface
• Several options / accessories provided with standard delivery:
o Sequence phase control safe electric installation
o Electronic expansion valve precision in SH control
o Control circuit transformer power supply without neutral
o Control data logger thermodynamic parameters recording
o Water differential pressure switch protection against low water flow
o Antifreeze electrical heater protection against BPHE freezing