IOM SYSCROLL 400 900 J36756

51
English
8 - Technical Data (continued)
8.3 Unit electrical data
SYSCROLL AIR EVO CO/TR 400 450 490 530 600 670 750 800 850 900
Rated voltage V/ph/Hz 400 / 3 / 50
Max. absorbed power kW 191 215 236 257 289 321 362 382 406 430
Rated Current A 226 254 281 308 343 377 431 452 480 508
Max. current FLA A 325 363 403 443 492 541 620 650 688 726
Max. start-up current LRA A 542 580 624 664 709 758 837 867 905 943
External fuses A 400 400 630 630 630 630 800 800 800 800
Max. cable section (*) mm
2
240 240 2x185 2x185 2x185 2x185 2x240 2x240 2x240 2x240
SYSCROLL AIR EVO CO/TR SLN 400 450 490 530 600 670 750 800 850
Rated voltage V/ph/Hz 400 / 3 / 50
Max. absorbed power kW 187 209 229 249 281 312 354 374 396
Rated Current A 215 239 264 290 322 354 409 429 453
Max. current FLA A 314 348 386 424 471 518 598 628 662
Max. start-up current LRA A 531 565 607 645 688 735 815 845 879
External fuses A 400 400 630 630 630 630 800 800 800
Max. cable section (*) mm
2
240 240 2x185 2x185 2x185 2x185 2x240 2x240 2x240
SYSCROLL AIR EVO CO/TR SLN EC version 400 450 490 530 600 670 750 800 850
Rated voltage V/ph/Hz 400 / 3 / 50
Max. absorbed power kW 196 219 240 261 293 325 371 391 415
Rated Current A 228 254 281 308 341 375 435 455 482
Max. current FLA A 327 364 403 442 491 539 624 654 691
Max. start-up current LRA A 544 581 624 663 708 756 841 871 908
External fuses A 400 400 630 630 630 630 800 800 800
Max. cable section (*) mm
2
240 240 2x185 2x185 2x185 2x185 2x240 2x240 2x240
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature in the room,
the type of insulation and the cable laying, the maximum length of the power supply line.
SYSCROLL AIR EVO CO/TR EC version 400 450 490 530 600 670 750 800 850 900
Rated voltage V/ph/Hz 400 / 3 / 50
Max. absorbed power kW 192 216 236 257 289 321 363 383 407 431
Rated Current A 221 248 275 301 335 368 422 442 469 496
Max. current FLA A 320 357 396 436 484 532 611 641 677 714
Max. start-up current LRA A 537 574 617 657 701 749 828 858 894 931
External fuses A 400 400 630 630 630 630 800 800 800 800
Max. cable section (*) mm
2
240 240 2x185 2x185 2x185 2x185 2x240 2x240 2x240 2x240
SYSCROLL AIR EVO CO/TR HPF version 400 450 490 530 600 670 750 800 850 900
Rated voltage V/ph/Hz 400 / 3 / 50
Max. absorbed power kW 201 227 249 271 304 337 382 402 428 454
Rated Current A 233 263 291 319 354 389 446 466 496 526
Max. current FLA A 332 372 413 454 503 553 635 665 704 744
Max. start-up current LRA A 549 589 634 675 720 770 852 882 921 961
External fuses A 400 400 630 630 630 630 800 800 800 800
Max. cable section (*) mm
2
240 240 2x185 2x185 2x185 2x185 2x240 2x240 2x240 2x240
SYSCROLL AIR EVO CO/TR HT version 400 450 490 530 600 670 750 800 850
Rated voltage V/ph/Hz 400 / 3 / 50
Max. absorbed power kW 207 233 255 277 311 344 394 414 440
Rated Current A 243 272 301 329 364 399 465 485 515
Max. current FLA A 342 382 422 463 513 563 654 684 724
Max. start-up current LRA A 559 599 643 684 730 780 871 901 941
External fuses A 400 400 630 630 630 630 800 800 800
Max. cable section (*) mm
2
240 240 2x185 2x185 2x185 2x185 2x240 2x240 2x240