Electrical Data
Main unit data: HP units 400 V / 3 ph / 50 Hz
SYSCROLL AIR EVO
HP
S version
Nominal input
current
Total input
current
Nominal input
power
Total input
power
Start-up
current
Unit
fuses
Phase wire
section
A A kW kW A A mm
2
400 242 339 137 183 664 400 240
450 268 377 153 203 703 400 240
490 293 412 167 223 657 630 2x185
530 319 447 180 243 692 630 2x185
580 349 489 198 265 734 630 2x185
620 376 528 214 285 853 630 2x185
670 402 566 229 304 891 630 2x185
750 457 640 259 347 965 800 2x240
800 483 678 274 366 1003 800 2x240
SYSCROLL AIR EVO
HP
EC S version
Nominal input
current
Total input
current
Nominal input
power
Total input
power
Start-up
current
Unit
fuses
Phase wire
section
A A kW kW A A mm
2
400 235 332 138 184 658 400 240
450 261 370 153 203 695 400 240
490 286 404 167 224 649 630 2x185
530 310 439 181 244 683 630 2x185
580 339 480 199 266 724 630 2x185
620 365 517 214 285 843 630 2x185
670 391 555 230 305 880 630 2x185
750 444 627 260 348 952 800 2x240
800 470 665 275 367 990 800 2x240