EDM SYSCROLL 400 900 AIR EVO

SYSCROLL 400-900 AIR EVO
|
13
Operating Limits - SYSCROLL AIR EVO CO - Cooling Mode
Operating limits
1
For leaving uid temperature lower than -3 °C BC (Brine cooling) customization must be selected
2
Allowed tolerance on voltage supply: +/- 10%
SYSCROLL AIR EVO CO
400 450 490 530 600 670 750 800 850 900
Liquid
Leaving uid
temperature range
Water
°C
from +5 to +18
Water with glycol
1
°C
from-10 to +5
Temperature drop
K
from 3 to 7
Maximum operating pressure
bar
6
Ambient
tempera-
ture
Entering air tem-
perature range in
full load operation
-/EC
°C
from +10 to +48
S/EC S °C from-18 to +48
HT
°C
from-18 to +52
Recommended system chilled water volume
l
1.196 1.338 1.170 1.068 1.194 1.335 1.122 1.197 1.271 1.345
Minimum capacity step % 21 25 24 17 14 17 12 11 10 13
Unite power supply
2
V/ph/Hz
400/3/50