Physical Data - SYSCROLL AIR EVO CO HT - High temperature version
Main data
Model 400 450 490 530 600 670 750 800 850
Nominal cooling capacity
1
kW 411,2 455,8 497,3 543,1 607,2 678,7 768,3 820,5 867,0
Nominal input power
1
kW 123,4 138,4 152,2 167,3 186,4 208,9 234,2 249,2 265,0
EER
1
kW/kW 3,33 3,29 3,27 3,25 3,26 3,25 3,28 3,29 3,27
EUROVENT energy classication
1
A A A A A A A A A
EER 75% kW/kW 3,85 3,87 3,90 3,80 3,85 3,85 3,80 3,70 3,77
EER 50% kW/kW 4,61 4,67 4,74 4,46 4,47 4,65 4,52 4,52 4,55
EER 25% kW/kW 5,11 5,15 5,24 5,01 5,05 5,23 4,88 4,92 4,92
SEER
4
/ h
sc
4
4,78/188 4,83/190 4,80/189 4,83/190 4,85/191 4,85/191 4,7/185 4,63/182 4,9/193
Number of refrigerant circuits 2 2 2 2 2 2 4 4 4
Minimum capacity step % 21 25 24 17 14 17 12 11 10
Compressor
Number 4 4 5 6 6 6 8 8 8
Type Scroll
Oil type PVE
N°of loading stages 0 / 100
Evaporator
Number 1 1 1 1 1 1 2 2 2
Type Brazed plates heat exchanger
Water ow m
3
/h 70,9 78,6 85,8 93,8 104,8 117,1 132,7 141,8 149,9
Pressure drop kPa 28,0 34,0 40,0 48,0 51,0 43,0 60,0 68,0 75,0
Water volume l 43,7 49,1 49,1 49,1 53,6 54,3 80,2 87,4 92,8
Antifreeze Heater W 130 2 x 130
Air cooled condenser
Number of coils 10 12 13 14 15 16 20 20 22
Total face area per coil m
2
2,3
Fans
Number of fans 10 12 13 14 15 16 20 20 22
Nominal speed rpm 900
Total airow m³/h 220.000 264.000 286.000 308.000 330.000 352.000 440.000 440.000 484.000
Total input power kW 13,3 16,0 17,3 18,6 20,0 21,3 26,6 26,6 29,3
Water Connections (Evaporator)
Type Victaulic
Inlet / Outlet diameter inch 4" / 4" 5" / 5" 6" / 6"
Water Connections (Desuperheater)
Type Male GAS Threaded
Inlet / Outlet diameter inch 1"1/4 / 1"1/4 2" / 2" 1"1/4 / 1"1/4
Weight
Shipping kg 3.220 3.546 3.959 4.259 4.477 4.664 5.935 5.992 6.296
Operating kg 3.318 3.656 4.069 4.369 4.597 4.789 6.111 6.183 6.499
Dimensions
Length mm 5.620 6.680 7.760 7.760 8.800 8.800 11.000 11.000 12.050
Width mm 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175 2.175
Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
Sound data
Sound power level
2
dB(A) 93 93 94 94 94 95 96 96 96
Sound pressure level - (10m)
3
dB(A) 60 61 60 61 61 61 62 62 62
1
Water / Plant side heat exchanger: RWT = 12 °C / LWT = 7 °C. Air / Source side heat exchanger: OAT = 35 °C. Declared data are in accordance with EN14511
2
Sound power level is declared in nominal full load condition (cooling operation), referring to ISO standard 9614, in accordance with Eurovent certication program
3
Sound pressure level refer to ISO Standard 3744, parallelepiped shape in a free eld on a reective surface
4
According to EN14825 and following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers