Model 140 170 230 260 280 300 330 360
Nominal cooling capacity (1) kW 133 149 207 237 253 279 299 330
Input power (1) kW 45,2 55,3 73,7 83,7 91,4 99,1 103,1 117,5
EER/ Energy Efciency Class (1) 2,94/B 2,70/C 2,81/C 2,83/C 2,77/C 2,82/C 2,90/C 2,81/C
EER (*) /Energy Efciency Class (*) (1) 2,98/B 2,73/C 2,85/C 2,87/C 2,81/C 2,86/C 2,94/B 2,84/C
SEER (3) 3,8 3,95 4,13 4,05 4,1 3,83 3,8 3,93
h
sc
(3)
149 155 162 159 161 150 149 154
SEER(*)(3) 4,58 4,65 3,7 3,65 3,63 2,58 2,65 4,17
h
sc
(*)(3)
180 183 145 143 142 100 103 164
Nominal heating capacity (2) kW 141 162 224 256 272 299 321 354
Input power (2) kW 43,5 50,3 69,0 79,4 84,8 92,7 99,6 109,9
COP/ Energy Efciency Class (2) 3,24/A 3,22/A 3,24/A 3,22/A 3,21/A 3,23/A 3,22/A 3,22/A
Nominal heating capacity (6) kW 144 166 228 261 277 304 326 359
Input power (6) kW 35,8 42,2 56,5 65,2 69,8 75,2 81,0 89,8
COP / COP (*) (6) 4,03/3,32 3,93/3,30 4,03/3,32 4,00/3,31 3,97/3,29 4,04/3,31 4,03/3,31 4,00/3,30
SCOP /Energy efciency class /
h
sh
(7)
3,39/A+/
133
3,42/A+/
134
3,46/A+/
135
3,48/A+/
136
3,44/A+/
135
3,51/A+/
137
3,44/A+/
135
3,48/A+/
136
Number of refrigerant circuits 2 2 2 2 2 2 2 2
Total capacity steps %
25-50-75-
100
25-50-75-
100
19-38-69-
100
17-39-67-
100
16-37-68-
100
24-48-71-
100
23-50-73-
100
25-50-75-
100
Compressor
Number 4 4 4 4 4 4 4 4
Type / Oil type Scroll / Poe
Evaporator
Number 1 1 2 2 2 1 1 1
Type Plate Plate Plate Plate Plate Plate Plate Plate
Water ow Cooling m
3
/h 22,9 25,8 35,7 40,9 43,7 48,2 51,6 57,0
Water pressure drop Cooling kPa 23 29 28 28 33 25 28 34
Water ow Heating (2) m
3
/h 24,2 27,8 38,4 43,8 46,7 51,4 55,0 60,7
Water pressure drop Heating (2) kPa 26 34 33 33 37 28 32 39
Water ow Heating (6) m
3
/h 24,7 28,4 39,0 44,7 47,5 52,1 56,0 61,6
Water pressure drop Heating (6) kPa 27 36 34 34 39 29 33 40
Water volume l 11,4 11,4 21,1 23,4 23,4 32,4 32,4 32,4
Antifreeze Heater W 130 130 130+130 130+130 130+130 130 130 130
Air cooled condenser
Number of coils 2 2 5 6 6 7 8 8
Total coil face area per coil m
2
4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4
Fans
Number of fans 3 3 5 6 6 7 8 8
Nominal speed rpm 700 700 700 700 700 700 700 700
Total airow m
3
/h 55.000 55.000 92.500 111.000 111.000 129.500 148.000 148.000
Total input power kW 3,6 3,6 6,0 7,2 7,2 8,4 9,6 9,6
Water Connections (Evaporator)
Type Male GAS Threaded
Inlet Diameter inch 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”
Outlet Diameter inch 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”
Water Connections (Desuperheater)
Type Male GAS Threaded
Inlet Diameter inch 1” 1” 1” 1” 1” 1” 1” 1”
Outlet Diameter inch 1” 1” 1” 1” 1” 1” 1” 1”
Weight
Shipping kg 1.294 1.337 2.049 2.312 2.427 2.564 2.748 2.925
Operating kg 1.312 1.355 2.078 2.343 2.458 2.702 2.887 3.063
Additional weight
EC kg 30 30 50 60 60 70 80 80
Desuperheater versions kg 8,5 8,5 17 19 19 23 23 23
Dimensions
Length mm 4.000 4.000 3.500 3.500 3.500 4.550 4.550 4.550
Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150
Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
Acoustical data
Sound power level (4) dB(A) 85 85 87 88 88 89 90 90
Sound pressure level - (10m) (5) dB(A) 53 53 55 56 56 57 58 58
Physical Data - SYSCROLL AIR EVO HP_L (STD-EC)
Standard and Inverter Fans versions
(1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air
temperature, NET value refear to EN14511.
(2) Data refers to 45°C leaving warm water temperature and 7°C ambient coil air
temperature with 87% R.H., NET value refear to EN14511.
(3) Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application
chillers.
(4) Sound levels are at fully loaded conditions. Sound power level values refear to ISO
standard 3744 and Eurovent 8/1.
(5) Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
(6) Data refers to 35 °C leaving warm water temperature and 7 °C ambient coil
air temperature with 87% R.H., NET value refear to EN14511, according to DM
28_12_12.
(7) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat
pumps.
(*) High Efciency Units (EC) with inverter fans.