IOM SyScroll 140 360 Air EVO 361549

48
8 - Technical Data (continued)
SYSCROLL AIR EVO HP_S 140 170 230 260 280 300 330 360
Power supply V/ph/Hz 400V/3/50Hz
Total capacity steps %
25-50-
75-100
25-50-
75-100
19-38-
69-100
17-39-
67-100
16-37-
68-100
24-48-
71-100
23-50-
73-100
25-50-
75-100
REFRIGERANT
Type / GWP R410A / 2.088
Charge Circuit One (3)
kg 23 23.5 27 28 28 43 53 54
tCO
2
eq 48.0 49.1 56.4 58.5 58.5 89.8 110.7 112.8
Charge Circuit Two (3)
kg 23 23.5 42.5 52 54 55 53 54
tCO
2
eq 48.0 49.1 88.7 108.6 112.8 114.8 110.7 112.8
COMPRESSOR
Number 4 4 4 4 4 4 4 4
Type / Oil type Scroll / POE
N° of loading stages 0/100 0/100 0/100 0/100 0/100 0/100 0/100 0/100
EVAPORATOR
Number 1 1 2 2 2 1 1 1
Type Plate
Water flow Cooling m
3
/h 21.7 24.2 33.6 38.6 41.1 45.4 48.9 53.6
Water pressure drop Cooling kPa 21 26 25 25 29 22 25 30.3
Water flow Heating (1) m
3
/h 23.8 27.3 37.7 43.0 45.8 50.6 54.0 59.8
Water pressure drop Heating (1) kPa 25 33 32 32 36 27 31 38
Water flow Heating (2) m
3
/h 24.2 27.9 38.3 43.8 46.5 51.2 54.8 60.5
Water pressure drop Heating (2) kPa 26 34 33 33 37 28 32 39
Water volume l 11.4 11.4 21.1 23.4 23.4 32.4 32.4 32.4
Antifreeze Heater W 130 130 130+130 130+130 130+130 130 130 130
AIR COOLED CONDENSER
Number of coils 2 2 5 6 6 7 8 8
Total coil face area per coil m
2
4.6 4.6
2.4 2.4 2.4
2.4
2.4 2.4
FANS
Number of fans 3 3 5 6 6 7 8 8
Nominal speed rpm 550 550 550 550 550 550 550 550
Total airflow m
3
/h 44.000 44.000 72.500 87.000 87.000 101.500 116.000 116.000
Total input power kW 2.7 2.7 4.5 5.4 5.4 6.3 7.2 7.2
WATER CONNECTIONS (EVAPORATOR)
Type Male GAS Threaded
Inlet Diameter / Outlet Diameter inch 2”1/2 / 2”1/2 3” / 3”
WATER CONNECTIONS (DESUPERHEATER)
Type Male GAS Threaded
Inlet Diameter / Outlet Diameter inch 1” / 1”
WEIGHT
Shipping kg 1.299 1.342 2.054 2.317 2.432 2.569 2.753 2.930
Operating kg 1.317 1.360 2.083 2.348 2.463 2.707 2.892 3.068
ADDITIONAL WEIGHT
EC kg 30 30 50 60 60 70 80 80
Desuperheater versions kg 8.5 8.5 17 19 19 23 23 23
DIMENSIONS
Length mm 4.000 4.000 3.500 3.500 3.500 4.550 4.550 4.550
Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150
Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
(1) Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., NET value refear to EN14511.
(2) Data refers to 35 °C leaving warm water temperature and 7 °C ambient coil air temperature with 87% R.H., NET value refear to EN14511, according to DM
28_12_12.
(3) The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.