Model 140 170 230 260 280 300 330 360
Nominal cooling capacity (1) kW 138 156 216 249 263 290 310 343
Input power (1)(3) kW 39,0 48,4 63,2 71,9 78,6 84,9 88,0 101,0
EER/ Energy Efciency Class (1) 2,92/B 2,75/C 2,80/C 2,78/C 2,77/C 2,80/C 2,82/C 2,79/C
SEER (6) 3,95 4,08 4,22 4,13 4,2 3,93 3,8 4,05
h
sc
(6)
155 160 166 162 165 154 149 159
Nominal heating capacity (2) kW 147 169 232 266 284 310 332 367
Input power (2)(3) kW 39,2 46,0 61,8 70,7 76,1 82,3 87,1 97,8
COP (2) 3,11 3,12 3,10 3,07 3,08 3,08 3,06 3,08
Energy Efciency Class B B B B B B B B
Nominal heating capacity (7) kW 151 173 238 273 291 316 339 374
Input power (7)(3) kW 31,6 37,9 49,4 56,7 61,2 65,0 69,0 77,8
COP (7) 3,79 3,73 3,76 3,73 3,73 3,76 3,73 3,74
SCOP /Energy efciency class /
h
sh
(8)
3,55/A+/
139
3,58/A+/
140
3,56/A+/
139
3,57/A+/
140
3,53/A+/
138
3,61/A+/
141
3,55/A+/
139
3,58/A+/
140
Number of refrigerant circuits 2 2 2 2 2 2 2 2
Total capacity steps %
25-50-75-
100
25-50-75-
100
19-38-69-
100
17-39-67-
100
16-37-68-
100
24-48-71-
100
23-50-73-
100
25-50-75-
100
Compressor
Number 4 4 4 4 4 4 4 4
Type / Oil type Scroll / Poe
Evaporator
Number 1 1 2 2 2 1 1 1
Type Plate Plate Plate Plate Plate Plate Plate Plate
water ow Cooling m
3
/h 23,8 26,9 37,2 42,4 45,5 50,1 53,4 59,3
Water pressure drop Cooling kPa 25 32 31 31 35 26 30 37
Water ow Heating (2) m
3
/h 25,2 28,9 39,8 45,6 48,6 53,1 56,8 62,8
Water pressure drop Heating (2) kPa 28 37 35 35 40 30 34 42
Water ow Heating (7) m
3
/h 25,9 29,7 40,8 46,8 49,8 54,2 58,1 64,1
Water pressure drop Heating (7) kPa 30 39 37 37 42 31 36 43
Water volume l 11,4 11,4 21,1 23,4 23,4 32,4 32,4 32,4
Antifreeze Heater W 130 130 130+130 130+130 130+130 130 130 130
Air cooled condenser
Number of coils 5 5 6 6 6 7 8 8
Total coil face area per coil m
2
12 12 14,4 14,4 14,4 16,8 19,2 19,2
Fans
Number of fans 3 3 5 6 6 7 8 8
Nominal speed rpm 1.100 1.100 1.100 1.100 1.100 1.100 1.100 1.100
Total airow m
3
/h 80.500 80.500 132.500 159.000 159.000 185.500 212.000 212.000
Total input power (*) kW 7,8 7,8 13,0 15,6 15,6 18,2 20,8 20,8
Water Connections (Evaporator)
Type Male GAS Threaded
Inlet Diameter inch 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”
Outlet Diameter inch 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”
Water Connections (Desuperheater)
Type Male GAS Threaded
Inlet Diameter inch 1” 1” 1” 1” 1” 1” 1” 1”
Outlet Diameter inch 1” 1” 1” 1” 1” 1” 1” 1”
Weight
Shipping kg 1.324 1.367 2.099 2.372 2.487 2.634 2.828 3.005
Operating kg 1.342 1.385 2.128 2.403 2.518 2.772 2.967 3.143
Additional weight
Desuperheater versions kg 8,5 8,5 17 19 19 23 23 23
Dimensions
Length mm 4.000 4.000 3.500 3.500 3.500 4.550 4.550 4.550
Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150
Height mm 2.500 2.500 2.500 2.500 2.500 2.500 2.500 2.500
Acoustical data
Sound power level (4) dB(A) 92 92 94 96 96 97 98 98
Sound pressure level - (10m) (5) dB(A) 60 60 62 64 64 65 66 66
(1) Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, NET value refear to EN14511.
(2) Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., NET value refear to EN14511.
(3) Input power (only compressors).
(4) Sound levels are at fully loaded conditions. Sound power level values refear to ISO standard 3744 and Eurovent 8/1.
(5) Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
(6) Following COMMISSION REGULATION (EU) No 2016/2281 for comfort application chillers.
(7) Data refers to 35 °C leaving warm water temperature and 7 °C ambient coil air temperature with 87% R.H., NET value refear to EN14511.
(8) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps.
(*) High Efciency Units (EC) with inverter fans.
Physical Data - SYSCROLL AIR EVO HP_HT