EDM SYSCROLL 140 360 AIR EVO
|
SYSCROLL AIR EVO
14
Operating Limits - SYSCROLL AIR EVO HP Heating Mode
SYSCROLL AIR EVO HP
140 170 230 260
Min Max Min Max Min Max Min Max
Chilled
liquid
Liquid outlet
temperature
Water °C +5 to +18
Water with glycol (*)
°C
-10 to +5
Temperature spread
K
3 to 7
Maximum operating pressure bar 6
Warmed
Liquid
Liquid outlet
temperature
Water
°C
+20 to +55
Temperature spread
°K
3 to 7
Maximum operating pressure bar 6
Ambient
air
Air entering
temp. Heating
- / L / S
°C
-10 to +20 / -4 to +20 (L/S)
Polar version
°C
-13 to +20
EC-HT °C -13 to +20
External
static pressure
Standard fans
Pa
0
High pressure fans
Pa
<120
Recommended system chilled water volume (1) l 420 510 690 780
Minimum capacity step
%
25 25 19 17
Power supply voltage (2)
V
400 V / 3 Ø / 50 Hz (nominal)
Operating limits
(*) For Liquid outlet temperature <0 °C provide Brine Version (available for CO; on request for HP).
(1) Table shows minimum water / brine volume of system (about 3 lt/kW).
(2) Voltage 400V +/- 10%.
SYSCROLL AIR EVO HP
280 300 330 360
Min Max Min Max Min Max Min Max
Chilled
liquid
Liquid outlet
temperature
Water
°C
+5 to +18
Water with glycol (*) °C -10 to +5
Temperature spread
K
3 to 7
Maximum operating pressure
bar
6
Warmed
Liquid
Liquid outlet
temperature
Water °C +20 to +55
Temperature spread
°K
3 to 7
Maximum operating pressure
bar
6
Ambient
air
Air entering
temp. Heating
- / L / S °C -10 to +20 / -4 to +20 (L/S)
Polar version
°C
-13 to +20
EC-HT
°C
-13 to +20
External
static pressure
Standard fans Pa 0
High pressure fans
Pa
<120
Recommended system chilled water volume (1)
l
840 900 990 1080
Minimum capacity step % 16 24 23 25
Power supply voltage (2)
V
400 V / 3 Ø / 50 Hz (nominal)