EDM SYSFREECOOL

SysFreeCool
|
13
Operating Limits
*
SysFreeCool
12 14 22 23 24 32 33 34 43 44
Brine
Minimum temperature
1
°C
-10
Maximum operating pressure
bar
6
Min./Max.
Ambient
Outdoor air temperature °C -20 to +50
External
static pressure
Standard fans
Pa
0
High pressure fans
Pa
< 120
Power supply voltage
2
V 400 V, 3 Ø, 50 Hz (nominal)
*
Operating limits refer to free-cooling module. Concerning chiller to be matched to free-cooling module, operating limit can be found inside chiller engineering data manual.
1
Liquid with appropriate % of glycol.
2
Voltage 400V +/- 10%.