EDM SYSFREECOOL

|
SysFreeCool
14
Physical Data - SysFreeCool_ - (STD -HPF)
Model 12 14 22 23 24
Nominal capacity
1
kW 101 156 206 245 275
Nominal Water Flow m
3
/h 19,0 29,4 38,7 46,0 51,7
Total pressure drop
1
kPa 44 83 74 43 49
Fans
Number of fans 2 2 4 4 4
Nominal speed rpm 900 900 900 900 900
Total airow m
3
/h 45.400 41.000 90.000 85.200 80.400
Total input power kW 4,2 4,2 8,4 8,4 8,4
Total input power
*
kW 6,2 6,2 12,4 12,4 12,4
Water Connections
Type Male GAS Threaded
Inlet Diameter inch 2” 1/2 2” 1/2 2” 1/2 3” 3”
Outlet Diameter inch 2” 1/2 2” 1/2 2” 1/2 3” 3”
Water Flow Range
Min water ow m
3
/h 11,1 12,5 17,4 27,2 28,7
Max water ow m
3
/h 30,0 33,8 47,2 73,6 77,8
Weight
Shipping kg 624 664 912 965 1.005
Operating kg 669 733 1.002 1.075 1.139
Dimensions
Length mm 2.146 2.124
Width mm 1.097 2.146
Height mm 2.519 2.519
Acoustical data
Sound power level
2
dB(A) 88 88 91 91 91
Sound pressure level at 10 m
3
dB(A) 56 56 59 59 59
1
Data refers to 15 (°C) return brine temperature, 10 (°C) leaving brine temperature, 0 (°C) outdoor air temperature; 30% EG.
2
Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.
3
Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
* HPF version.