8.3 Unit electrical data
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working
temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
AQVL/AQVH STD 85 95 105 115 125 140
Rated voltage V/ph/Hz 400V(± 10%)/3/50Hz
Max. absorbed power kW 39 43 47 50 57 63
Rated Current 50 55 60 66 77 84
Max. current FLA A 68 88 90 92 114 132
Max. start-up current LRA A 147 178 186 188 223 241
External fuses A 100 100 125 125 125 160
Max. cable section (*) mm
2
50 50 50 50 70 70
Exchanger resistance
Rated voltage V/ph/Hz 230(± 10%)/1/50
Max. absorbed power W 130
AQVL/AQVH S 85 95 105 115 125 140
Rated voltage V/ph/Hz 400V(± 10%)/3/50Hz
Max. absorbed power kW 39 43 47 50 56 61
Rated Current 50 55 60 66 73 81
Max. current FLA A 68 88 90 92 110 128
Max. start-up current LRA A 147 178 186 188 219 237
External fuses A 100 100 125 125 125 160
Max. cable section (*) mm
2
50 50 50 50 70 70
Exchanger resistance
Rated voltage V/ph/Hz 230 (± 10%)/1/50
Max. absorbed power W 130
AQVL/AQVH HT/HSE/HPF 85 95 105 115 125 140
Rated voltage V/ph/Hz 400V(± 10%)/3/50Hz
Max. absorbed power kW 42 46 50 53 59 65
Rated Current 54 60 65 70 78 85
Max. current FLA A 73 93 95 97 115 133
Max. start-up current LRA A 152 183 191 193 224 242
External fuses A 100 100 125 125 125 160
Max. cable section (*) mm2 50 50 50 50 70 70
Exchanger resistance
Rated voltage V/ph/Hz 230 (± 10%)/1/50
Max. absorbed power W 130
Technical data