IOM AQV 85 140

Page 48
Technical data
AQVC
Al/Cu
Weight distribution
Ope-
rating
weight
Ship-
ping
weight
P1-P4 coordinates* CG coordinates
F1 F2 F3 F4 a b x y
kg kg kg kg kg kg mm mm mm mm
85 385 384 101 100 971 971 1039 1382 547 1584
95 391 390 101 101 983 983 1039 1382 547 1587
105 395 403 104 111 1013 1013 1039 1382 555 1578
115 408 407 114 114 1043 1043 1039 1382 547 1569
125 384 385 148 149 1066 1066 1039 1982 549 1920
140 406 405 166 165 1142 1142 1039 1982 547 1897
AQVC 85 - 140 Al/Cu Version STD/S/HT
AQVC
Cu/Cu
Weight distribution
Ope-
rating
weight
Ship-
ping
weight
P1-P4 coordinates* CG coordinates
F1 F2 F3 F4 a b x y
kg kg kg kg kg kg mm mm mm mm
85 438 437 155 154 1183 1183 1039 1382 546 1511
95 444 443 155 154 1196 1196 1039 1382 546 1514
105 453 468 162 178 1261 1261 1039 1382 560 1499
115 479 477 186 185 1326 1326 1039 1382 546 1484
125 454 454 217 217 1342 1342 1039 1982 548 1830
140 499 496 258 256 1509 1509 1039 1982 546 1796
AQVC 85 - 140 Cu/Cu Version STD/S/HT
* Dimensions are referred to unit with antivibration mounted isolators.
AQVC
MCHX
Weight distribution
Ope-
rating
weight
Shipping
weight
P1-P4 coordinates* CG coordinates
F1 F2 F3 F4 a b x y
kg kg kg kg kg kg mm mm mm mm
85 358 358 74 74 864 864 1039 1382 547 1635
95 364 364 74 74 876 876 1039 1382 547 1637
105 366 366 74 74 880 880 1039 1382 549 1639
115 368 368 74 74 884 884 1039 1382 547 1639
125 349 351 113 115 928 928 1039 1982 550 1985
140 354 354 114 114 935 935 1039 1982 547 1988
AQVC 85 - 140 MCHX
AQVC
Line length ø Suction line ø Liquid line R410A
m inch mm inch mm kg/m
85
10 1”3/8 34,93 7/8” 22,23 0,34
20 1”3/8 34,93 7/8” 22,23 0,34
30 1”3/8 34,93 7/8” 22,23 0,34
95
10 1”3/8 34,93 7/8” 22,23 0,34
20 1”3/8 34,93 7/8” 22,23 0,34
30 1”3/8 41,28 7/8” 22,23 0,35
105
10 1”3/8 34,93 7/8” 22,23 0,34
20 1”3/8 34,93 7/8” 22,23 0,34
30 1”5/8 41,28 7/8” 22,23 0,35
115
10 1”3/8 34,93 1”1/8 28,58 0,53
20 1”3/8 34,93 1”1/8 28,58 0,53
30 1”5/8 41,28 1”1/8 28,58 0,54
125
10 1”3/8 34,93 1”1/8 28,58 0,53
20 1”3/8 34,93 1”1/8 28,58 0,53
30 1”5/8 41,28 1”1/8 28,58 0,54
140
10 1”3/8 34,93 1”1/8 28,58 0,53
20 1”5/8 41,28 1”1/8 28,58 0,54
30 1”5/8 41,28 1”1/8 28,58 0,54
AQVC Refrigerant Lines
AQVC125: Max distance: consider 30mt. 30mt Suction line + 30mt Liquid line.
Each refrigerant circuit needed to add 0.53kg / mt of distance. In example in case of 30mt distance between AQVC and evaporator, for
each circuit consider 30x0.53kg = 15.9kg per circuit.