IOM AQV 85 140

Page 33
English
Technical data
AQVL S 85 95 105 115 125 140
Power supply V/ph/Hz 400V(± 10%)/3/50Hz
Number of refrigerant circuits 2 2 2 2 2 2
Total capacity steps %
0-25-50-75-
100
0-25-50-75-
100
0-24-47-74-
100
0-25-50-75-
100
0-22-43-72-
100
0-25-50-75-
100
Refrigerant
Type / GWP R410A / 2.088
Charge 1/2
(1)
kg 6 / 6 6 / 6 6 / 6 6 / 6 8 / 8 8 / 8
tCO
2
eq 12,5 / 12,5 12,5 / 12,5 12,5 / 12,5 12,5 / 12,5 16,7 / 16,7 16,7 / 16,7
Compressor
Type Scroll
Number 4 4 4 4 4 4
Start-up type Direct
Oil type POE
N°of loading stages 0/100 0/100 0/100 0/100 0/100 0/100
Evaporator
Type Plate
Number 1 1 1 1 1 1
Water flow rate l/s 3,9 4,3 4,7 5,1 5,7 6,4
Pressure drop kPa Refers to Hydraulic features
Desuperheater
Type Plate
Number 2 2 2 2 2 2
Water flow rate l/s 1,02 1,15 1,26 1,36 1,51 1,70
Pressure drop kPa Refers to Hydraulic features
Fans
Type Axial
Number 2 2 2 2 2 2
Nominal speed rpm 500 500 500 500 690 690
Air flow rate m³/s 7,00 7,00 6,83 6,7 10,1 9,7
Power input kW 1,8 1,8 1,8 1,8 2,1 2,1
Air cooled condenser
Type Coil
Number 2 2 2 2 2 2
Total coil face area per coil 2,4 2,4 2,4 2,4 3,1 3,1
Hydraulic connections (Evapora
-
tor)
Type Male Gas Threaded
Inlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 2”1/2 2”1/2
Outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 2”1/2 2”1/2
Hydraulic connections (Desu
-
perheater)
Type Male Gas Threaded
Inlet diameter inch 1” 1” 1” 1” 1” 1”
Outlet diameter inch 1” 1” 1” 1” 1” 1”
Weight
Shipping weight kg 1063 1077 1114 1146 1181 1260
Operating weight kg 1088 1102 1141 1173 1213 1292
Dimensions
Length mm 2555 2555 2555 2555 3155 3155
Width mm
1095
(1250)
1095
(1250)
1095
(1250)
1095
(1250)
1095
(1250)
1095
(1250)
Height mm 2185 2185 2185 2185 2185 2185
(1)
The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.