technical documentation manuals 308013008
Table Of Contents
- 1 General information
- 2 Important safety information
- 3 Warranty
- 4 Delivery, transport, storage
- 5 Description
- 6 Name plate and type key
- 7 Installation
- 8 Electrical connection
- 9 Commissioning
- 10 Operation
- 11 Troubleshooting/maintenance/repair
- 12 Cleaning
- 13 Deinstallation/dismantling
- 14 Disposal
- 15 Commissioning Report
22
|
Commissioning
9 Commissioning
Warranty claims can only be made if commissioning work is carried out correctly and written evidence thereof is
provided.
It is recommended to fill out the commissioning report chapter 15.
Safety information
♦ Commissioning may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 2.
Preconditions
♦ Installation and electrical connection have been
correctly performed.
♦ Residual material from installation and foreign objects
have been removed from the fan and ducts.
♦ Inlet and outlet are free.
♦ Safety devices have been fitted.
♦ Ground cable is connected.
♦ Cable glands are tight.
♦ Data on the name plate corresponds with the
connection data.
9.1 Tests
♦ Before switching the fan on, check for externally visible damage and ensure that the protective equipment functions
properly.
1. Switch the fan on.
2. Do the tests requested in the commissioning report (15 Commissioning Report, page 27)
Speed controllable fans: “Measured data at commissioning” at maximum speed
3. Switch the fan off.
9.2 Commissioning of speed-controlled fans
Check the fan for vibrations at all normal operation speeds during commissioning. Determine and evaluate vibrations
on the housing and bearing areas in accordance with DIN ISO 14694 depending on motor power and positioning.
Measurable vibration velocities depend e.g. on following factors:
• positioning
• bottom section/foundation state • flow conditions
The working point of the fan, as well as used external devices and accessories, also influence the running
characteristics.
9.3 Adjusting the blade angle
If the working point of the fan has to be changed and it is necessary to adjust the blade angle, please contact
Systemair!
10 Operation
Safety information
Warning: Hazard from electrical voltage or moving components.
♦ Operation may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 2.
Preconditions
♦ Ensure access only to persons who can safely handle the device.
♦ Only use the fan in accordance with the operating instructions and the operating instructions for the motor.
Speed-controlled fan operation
Please observe 8.3 Frequency converter (if used), page 21.
| 008