36/40 | User Manual S-SA2 & S-SA2L | 201905 201905 | User Manual S-SA2 & S-SA2L | 37/40
Recommended Course of Action and Inspection Log as per EN 12 101:
1. Identication of damper
2. Date of inspection
3. Check actuator wiring for damage
4. Check the wiring of the end switches for damage
5. Check the damper cleanliness and clean where necessary
6. Check the inspection lid, cover tightness
7. Check the blade and sealings, and correct and record where necessary (where applicable)
8. Check the damper functionality (open and close) as per the
“Smoke Damper Functionality Check” chapter
and conrm operation by using the control system, tracking the physical behavior of the damper and signalization
of the end positions, and correct and record where necessary (where applicable).
9. The damper is part of the SHEVS. Therefore, the complete system must be checked as specied in its operational
and maintenance requirements.
10. Set into the operating position – as per the
“Operation Manual” chapter.
11. Record the result into the
“Operating Journal” with the name and signature of the Inspection Technician.
Warranty Conditions
For warranty conditions, contact your local Systemair representative.
Functionality of every S-SA2 and S-SA2L smoke damper is tested in the production factory before being shipped.
Before you can install the re damper, its functionality must be tested as per the
“Smoke Damper Functionality
Check” chapter.
DO NOT INSTALL NON-FUNCTIONING SMOKE DAMPERS.
Changes of smoke damper functionality caused by transport or installation are not reclaimable after installation
(deformation, damages, mechanical damage of the sealing material, foreign objects which may constrain the blade
movement, incorrect handling of the activation mechanism, etc.).