Modbus Parameter Specifications

Table Of Contents
MODBUS ACE V1.00
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 10/6/2003 ·File: ext001931381.docx ·Last printed 9/30/2019 10:29:00
AM ·Page 35 of 78
Form 1003
2.10 Stored set value
Address : D00D
Write authorization : ebm-papst, customer, end customer
The information in this parameter is only of relevance if the value for the parameter "Set value source"
(holding register D101) is "RS485" (1) and the function "Store set value" (holding register D103) is active.
Otherwise this parameter has no function.
As the set value is located in the volatile memory, this value (if applicable) has to be saved in the non-volatile
memory as well to permit restarting with the last set value following interruption and restoration of the power
supply. The parameter "Stored set value" is intended for this purpose.
If the parameter "Set value" (holding register D001) is changed, the corresponding parameter "Stored set
value" is set to the same value if the function "Store set value" (holding register D103) is active.
The coding corresponds to the coding of the set value (holding register D001).
2.11 Enable RS485
Address : D00F
Write authorization : ebm-papst, customer, end customer
The information in this parameter is only of relevance if "Enable source" (holding register D16A) has the value
"RS485" (1).
If the "Store set value" parameter (holding register D103) has the "Store" function activated, the value is
transferred to the "Stored enable RS485" parameter (holding register D16B) in the event that the power
supply is interrupted. Once the power supply has been restored, the value of the parameter "Stored enable
RS485" will be transferred back to the parameter "Enable RS485" again.
Coding:
Value
Enable
0
Off (no enable)
1
On (enable)
Permissible value range: 0..1