Modbus Parameter Specifications
Table Of Contents
- Change history
- 1 Protocol frame
- 2 Holding registers
- 2.1 Overview
- 2.2 Reset
- 2.3 Set value
- 2.4 Password
- 2.5 Factory setting Control
- 2.6 Customer setting Control
- 2.7 Operating hours counter
- 2.8 Operating minutes counter
- 2.9 Addressing on/off
- 2.10 Stored set value
- 2.11 Enable RS485
- 2.12 Fan address
- 2.13 Set value source
- 2.14 Preferred running direction
- 2.15 Store set value
- 2.16 Mode of operation
- 2.17 Direction of action
- 2.18 Control parameters
- 2.19 Maximum modulation level
- 2.20 Minimum modulation level
- 2.21 Motor stop enable
- 2.22 Starting modulation level
- 2.23 Maximum permissible modulation level
- 2.24 Minimum permissible modulation level
- 2.25 Maximum speed
- 2.26 Maximum permissible speed
- 2.27 Ramp-up/ramp-down curve
- 2.28 Speed limit
- 2.29 Input characteristic curve
- 2.30 Maximum power
- 2.31 Maximum permissible power
- 2.32 Speed monitoring speed limit
- 2.33 Sensor actual value source
- 2.34 Interface settings
- 2.35 Rotating direction fail-safe mode
- 2.36 Fail-safe set value source
- 2.37 Set value for fail safe function
- 2.38 Time lag fail-safe speed
- 2.39 Cable break detection voltage
- 2.40 Sensor
- 2.41 Enable source
- 2.42 Stored enable RS485
- 2.43 Customer data
- 2.44 Error history
- 2.45 DC-link voltage reference value
- 2.46 DC-link current reference value
- 2.47 Manufacturing data
- 2.48 Air flow reference value
- 2.49 Mass flow reference value
- 2.50 Mirror function for holding registers
- 2.51 Mirror function for input registers
- 2.52 Mass flow calculation
- 3 Input registers
- 3.1 Overview
- 3.2 Identification
- 3.3 Maximum number of bytes
- 3.4 Bus controller software name
- 3.5 Bus controller software version
- 3.6 Commutation controller software name
- 3.7 Commutation controller software version
- 3.8 Actual speed
- 3.9 Motor status
- 3.10 Warning
- 3.11 DC-link voltage
- 3.12 DC-link current
- 3.13 Motor temperature
- 3.14 Temperature inside electronics
- 3.15 Current modulation level
- 3.16 Current set value
- 3.17 Sensor actual values
- 3.18 Enable input state
- 3.19 Current controller function
- 3.20 Current power
- 3.21 Current set value source
- 3.22 Energy consumption counter
- 3.23 Heartbeat
- 3.24 Mirrored input registers
MODBUS ACE V1.00
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 10/6/2003 ·File: ext001931381.docx ·Last printed 9/30/2019 10:29:00
AM ·Page 35 of 78
Form 1003
2.10 Stored set value
Address : D00D
Write authorization : ebm-papst, customer, end customer
The information in this parameter is only of relevance if the value for the parameter "Set value source"
(holding register D101) is "RS485" (1) and the function "Store set value" (holding register D103) is active.
Otherwise this parameter has no function.
As the set value is located in the volatile memory, this value (if applicable) has to be saved in the non-volatile
memory as well to permit restarting with the last set value following interruption and restoration of the power
supply. The parameter "Stored set value" is intended for this purpose.
If the parameter "Set value" (holding register D001) is changed, the corresponding parameter "Stored set
value" is set to the same value if the function "Store set value" (holding register D103) is active.
The coding corresponds to the coding of the set value (holding register D001).
2.11 Enable RS485
Address : D00F
Write authorization : ebm-papst, customer, end customer
The information in this parameter is only of relevance if "Enable source" (holding register D16A) has the value
"RS485" (1).
If the "Store set value" parameter (holding register D103) has the "Store" function activated, the value is
transferred to the "Stored enable RS485" parameter (holding register D16B) in the event that the power
supply is interrupted. Once the power supply has been restored, the value of the parameter "Stored enable
RS485" will be transferred back to the parameter "Enable RS485" again.
Coding:
Value
Enable
0
Off (no enable)
1
On (enable)
Permissible value range: 0..1