DVV F DVV 120 E8302 31 08 15

DVV Roof Fan 3
Input power P1
[kW]
Current
[A]
Max. airow
[m³/h]
R. p. m.
[min
-1
]
Sound pressure level
at 4/10 m [dB(A)]
Weight [kg]* Wiring diagram
IE1, IE2 IE3 no EMC EMC
1,5 (DVV/120: 1,3) 4,0 (DVV/120: 2,6)
8000
1460 (DVV/120: 1420)
66/59 89 4
2,2 (DVV/120: 2,0) 4,7 (DVV/120: 3,7)
10150
1442 (DVV/120: 1410)
68/61 91 4
2,6 5,4 10800 1445 69/62 93 4
2,7/1,1 5,4/2,3 10800/7250 1445/965 69/62 / 59/52 96 2
3,7 6,64 15000 1441 71/63 130 4
2,1 4,5 13600 940 64/58 123 4
6,4 11 20900 1461 75/69 150 1
6,9/2,3 11,9/4,6 20900/13600 1445/965 75/69 / 64/58 168 2
3,8 6,92 20300 932 66/60 224 4
12,9 22 31500 1461 76/70 260 261 1 5
14,4/4,3 25,1/8,3 31500/20300 1467/965 76/70 / 66/60 291 2
5,6 11,2 26500 955 71/64 225 1
6/3 14,8/8 26500/19800 985/736 71/64 / 65/57 297 2
18,5 34,6 40000 1461 83/75 372 400 1 5
19/5,9 35,4/17,1 40000/26500 1472/988 83/75 / 71/64 401 2
18,7/3 37/10,6 40000/19800 1470/743 83/75 / 65/57 401 3
6,5 12,8 32500 980 73/65 366 372 1 5
6,7/3,4 15,8/8,3 32500/25000 981/736 73/65 / 65/57 363 2
22,3 39 51000 1472 86/78 430 459 1 6
23/7,4 43/19,9 51000/32500 1475/990 86/78 / 73/65 471 2
24/3,3 39,8/10,4 51000/25000 1484/737 86/78 / 65/57 471 3
5 10,2 34000 730 66/58 359 1
11,1 21,4 45000 977 74/66 400 401 1 5
11,1/5,8 21,4/14,1 45000/34000 977/735 74/66 / 66/58 416 2
11,1/1,7 21,4/5,8 45000/22500 977/488 74/66 / 61/52 416 3
4,2 8,2 28000 733 67/59 344 1
9,1 18 37300 982 75/67 388 389 1 5
30,1 51 56000 1473 88/80 499 499 1 6
30,5/9,5 53,5/17,7 56000/37300 1458/987 88/80 / 75/67 519 2
30,5/4,6 53,5/15,5 56000/28000 1465/740 88/80 / 67/59 494 3
Insulation class, motor F; enclosure class, motor IP55Due to different motor suppliers the actual motor data and weight can sligtly deviate.
* F600 items are app. 5% hevier, exact data are on-line available
Type DVV/F400, F600-XS, XM, XL, XP
Normal ventilation + smoke and heat extract (dual use)
Type F400 up to 400°C/120 min (F400/120, F400/90,
F300, F200)
Type F600 up to 600°C/120 min (F600, F400/120)
Tested acc. to EN 12101-3 at ZAG, Ljubljana
CE-certication acc. to EN 12101-3, 2002-06 by BSI, UK
Meet ErP efciency goal for dual use fans
Other features as DVV/120
EMC protected items prepared for frequency control
EMC shielded cable from motor to service switch
Service switch with capability of connection of shielded
power supply cable
Additional marking ‘‘EMC’
Meet Regulation 640/2009
Items with IE3 motor built-in
Meet higher requirements up to 640/2009 regarding motor
efciency
Type DVV/120-XS, XM, XL, XP
Normal ventilation up to 120°C continuous operation
Vertical exhaust, suitable for coastal application
IE2 single speed high efciency motor, IE1 two speed or
8-pole motor
Service switch and PTC thermal protection built-in serial
Sucking side connection acc. EUROVENT
Meet ErP efciency goal
400°C
120min
120°C
120°C
600°C
120min