DataSheet OPTIMA LV R201905

Variable Air Volume Controllers | 3 / 24
Description
OPTIMA-LV-R (RI) is a Variable Air ow Volume (VAV) contoller installed in circular ducts for demand oriented
ventilation. It can operate in large air velocity range and it is especially intended for precise ow control at low air
ow velocities down to 0,2 m/s. It is pressure independent in range of 2 Pa to 600 Pa. The electronic controllers
can operate for air supply or air extract. Individual control operation or Master/Slave combination of multiple
controllers is possible.
Highlights
Extends the range of VAV controllers in low air ow velocity part – down to 0,2 m/s
Adaptive measurement probe for high efcient dynamic pressure readings on whole velocity range
Advanced algorithm for appropriate control at subliminal duct static pressure
Operable at p range 2 Pa … 600 Pa
Unprecedented control ratio V
max
/V
min
= 30/1 (0,2 m/s … 6 m/s)
Lowest possible cross section restriction for given pressure - /ow parameters >> low pressure loss, low noise
No straight duct in front or behind the VAV controller required. Installation immediately behind or
in front of
elbow or tee duct piece is possible.
Accuracy: app. 5% deation from measured value *
Leakage class 4C
Full set of operation and override functions (Open, Close, V
min
, V
max
)
On-board Bus communication port available
NOTE: * The air ow controller OPTIMA-LV-R (RI) utilizes a special control algorithm to protect the actuator from mechanical damage in low velocity ow.
100
0 62
0
v (m/s)
±Δ (%)
50
4
0,6
Diagram 1: ±Δ (%) deviation from measured value of air ow
velocity in the duct v (m/s)
p (Pa) Dynamic pressure on ow measurement probe
V
min
Minimum limit of the air ow control range
V
max
Maximum limit of the air ow control range
±Δ (%) Deviation from measured value
v (m/s) Air ow velocity in the duct
Legend