Variable Air Volume Controllers | 3 / 24
Description
OPTIMA-LV-R (RI) is a Variable Air ow Volume (VAV) contoller installed in circular ducts for demand oriented
ventilation. It can operate in large air velocity range and it is especially intended for precise ow control at low air
ow velocities down to 0,2 m/s. It is pressure independent in range of 2 Pa to 600 Pa. The electronic controllers
can operate for air supply or air extract. Individual control operation or Master/Slave combination of multiple
controllers is possible.
Highlights
• Extends the range of VAV controllers in low air ow velocity part – down to 0,2 m/s
• Adaptive measurement probe for high efcient dynamic pressure readings on whole velocity range
• Advanced algorithm for appropriate control at subliminal duct static pressure
• Operable at ∆p range 2 Pa … 600 Pa
• Unprecedented control ratio V
max
/V
min
= 30/1 (0,2 m/s … 6 m/s)
• Lowest possible cross section restriction for given pressure - /ow parameters >> low pressure loss, low noise
• No straight duct in front or behind the VAV controller required. Installation immediately behind or
in front of
elbow or tee duct piece is possible.
• Accuracy: app. 5% deation from measured value *
• Leakage class 4C
• Full set of operation and override functions (Open, Close, V
min
, V
max
)
• On-board Bus communication port available
NOTE: * The air ow controller OPTIMA-LV-R (RI) utilizes a special control algorithm to protect the actuator from mechanical damage in low velocity ow.
100
0 62
0
v (m/s)
±Δ (%)
50
4
0,6
Diagram 1: ±Δ (%) deviation from measured value of air ow
velocity in the duct v (m/s)
∆p (Pa) Dynamic pressure on ow measurement probe
V
min
Minimum limit of the air ow control range
V
max
Maximum limit of the air ow control range
±Δ (%) Deviation from measured value
v (m/s) Air ow velocity in the duct
Legend