MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 28 of 70
Form 1003
2.2 Reset
Address : D000
Write authorisation : ebm-papst, customer, end customer
Encoding:
MSB
0
0
0
0
0
0
0
0
LSB
0
0
0
0
Reset
Error
Parameter
AWS Rst
A bit will trigger the following action in the fan when it is set:
Reset : Software reset (includes "Reset error" and "Adopt parameters")
The software is launched at the start of booting
Error : Errors are reset
Parameter : All parameters are copied from the EEPROM into the RAM
This bit must be set to make revised parameters valid
Reset AWS : User software reset
(includes "Reset error" and "Adopt parameters")
The software is reinitialised
After the action has been executed, the bit will automatically be reset by the fan.
When reset (bit 3), the program will be relaunched at the start of booting. Commands from the master will then
be neither responded to nor executed for a few seconds.
Reset (bit 3) is only recommended if new user software is to be loaded using a bootloader (because
communication is interrupted).
If only the software is to be reinitialised, user software reset (bit 0) is recommended. Then communication is
not interrupted.