Drive P22K P30K P37K P45K P55K P75K P90K
Continuous (3x380–440 V) [A] 35.2 48.8 58.4 63.0 74.2 102.9 123.9
Intermittent (3x380–440 V) [A] 38.7 53.9 64.2 69.3 81.6 113.2 136.3
Continuous (3x441–480 V) [A] 32.0 41.6 52.0 56.0 73.5 91.0 112.0
Intermittent (3x441–480 V) [A] 35.2 45.8 57.2 61.6 80.9 100.1 123.2
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consump-
tions are included. For power loss data according to EN 50598-2, refer to Danfoss
MyDrive® ecoSmart
TM
website.
2
Efficiency measured at nominal current. For energy efficiency class, see 6.4.13 Ambient Conditions. For part load losses, see Danfoss MyDrive® ecoSmart
TM
website.
6.1.3 3x525–600 V AC
Table 26: 3x525–600 V AC, 2.2–15 kW (3–20 hp), Enclosure Sizes H9–H10
Drive P2K2 P3K0 P3K7 P5K5 P7K5 P11K P15K
Typical shaft output [kW] 2.2 3.0 3.7 5.5 7.5 11.0 15.0
Typical shaft output [hp] 3.0 4.0 5.0 7.5 10.0 15.0 20.0
Protection rating IP20 H9 H9 H9 H9 H9 H10 H10
Maximum cable size in terminals
(mains, motor) [mm
2
(AWG)]
4 (10) 4 (10) 4 (10) 4 (10) 4 (10) 10 (8) 10 (8)
Output current - 40°C (104°F) ambient temperature
Continuous (3x525–550 V) [A] 4.1 5.2 6.4 9.5 11.5 19.0 23.0
Intermittent (3x525–550 V) [A] 4.5 5.7 7.0 10.5 12.7 20.9 25.3
Continuous (3x551–600 V) [A] 3.9 4.9 6.1 9.0 11.0 18.0 22.0
Intermittent (3x551–600 V) [A] 4.3 5.4 6.7 9.9 12.1 19.8 24.2
Maximum input current
Continuous (3x525–550 V) [A] 3.7 5.1 5.0 8.7 11.9 16.5 22.5
Intermittent (3x525–550 V) [A] 4.1 5.6 6.5 9.6 13.1 18.2 24.8
Continuous (3x551–600 V) [A] 3.5 4.8 5.6 8.3 11.4 15.7 21.4
Intermittent (3x551–600 V) [A] 3.9 5.3 6.2 9.2 12.5 17.3 23.6
Maximum mains fuses See 3.2.4.5 Recommendation of Fuses and Circuit Breakers.
Estimated power loss [W], best
case/typical
(1)
65 90 110 132 180 216 294
Weight enclosure protection rat-
ing IP54 [kg (lb)]
6.6 (14.6) 6.6 (14.6) 6.6 (14.6) 6.6 (14.6) 6.6 (14.6) 11.5 (25.3) 11.5 (25.3)
Efficiency [%], best case/typical
(2)
97.9 97 97.9 98.1 98.1 98.4 98.4
Output current - 50°C (122°F) ambient temperature
Continuous (3x525–550 V) [A] 2.9 3.6 4.5 6.7 8.1 13.3 16.1
Intermittent (3x525–550 V) [A] 3.2 4.0 4.9 7.4 8.9 14.6 17.7
Specifications
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 71