6.4 General Technical Data
6.4.1 Protection and Features
Electronic motor thermal protection against overload.
Temperature monitoring of the heat sink ensures that the drive trips if there is overtemperature.
The drive is protected against short circuits between motor terminals U, V, W.
When a motor phase is missing, the drive trips and issues an alarm.
When a mains phase is missing, the drive trips or issues a warning (depending on the load).
Monitoring of the DC-link voltage ensures that the drive trips when the DC-link voltage is too low or too high.
The drive is protected against ground faults on motor terminals U, V, W.
6.4.2 Mains Supply (L1, L2, L3)
Supply voltage 200–240 V ±10%
Supply voltage 380–480 V ±10%
Supply voltage 525–600 V ±10%
Supply frequency 50/60 Hz
Maximum imbalance temporary between mains phases 3.0% of rated supply voltage
True power factor (λ) ≥0.9 nominal at rated load
Displacement power factor (cosφ) near unity (>0.98)
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H1–H5, I2, I3, I4 Maximum 1 time/30 s
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H6–H10, I6–I8 Maximum 1 time/minute
Environment according to EN 60664-1 Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100000 A
rms
symmetrical Amperes, 240/480 V maximum.
6.4.3 Motor Output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency 0–400 Hz
Switching on output Unlimited
Ramp times 0.05–3600 s
6.4.4 Cable Length and Cross-section
Maximum motor cable length, shielded/armored (EMC-correct installation) See 6.2 EMC Emission Test Results.
Maximum motor cable length, unshielded/unarmoured 50 m (164 ft)
Maximum cross-section to motor, mains See 6.1.2 3x380–480 V AC for more information
Cross-section DC terminals for filter feedback on enclosure sizes H1–H3, I2, I3, I4
4 mm
2
/11 AWG
Cross-section DC terminals for filter feedback on enclosure sizes H4–H5
16 mm
2
/6 AWG
Maximum cross-section to control terminals, rigid wire
2.5 mm
2
/14 AWG
Maximum cross-section to control terminals, flexible cable
2.5 mm
2
/14 AWG