Manual
Table Of Contents
- VLT® HVAC Basic Drive FC 101
- English US
- Contents
- Introduction
- Safety
- Installation
- Mechanical Installation
- Electrical Installation
- Electrical Installation in General
- IT Mains
- Mains and Motor Connection
- Introduction
- Connecting to Mains and Motor
- Relays and Terminals on Enclosure Sizes H1–H5
- Relays and Terminals on Enclosure Size H6
- Relays and Terminals on Enclosure Size H7
- Relays and Terminals on Enclosure Size H8
- Connecting to Mains and Motor for Enclosure Size H9
- Relays and Terminals on Enclosure Size H10
- Enclosure Size I2
- Enclosure Size I3
- Enclosure Size I4
- IP54 Enclosure Sizes I2, I3, I4
- Enclosure size I6
- Enclosure size I7, I8
- Fuses and Circuit Breakers
- EMC-correct Electrical Installation
- Control Terminals
- Electrical Wiring
- Acoustic Noise or Vibration
- Programming
- Warnings and Alarms
- Specifications
- Index
- English US
6.4 General Technical Data
6.4.1 Protection and Features
• Electronic motor thermal protection against overload.
• Temperature monitoring of the heat sink ensures that the drive trips if there is overtemperature.
• The drive is protected against short circuits between motor terminals U, V, W.
• When a motor phase is missing, the drive trips and issues an alarm.
• When a mains phase is missing, the drive trips or issues a warning (depending on the load).
• Monitoring of the DC-link voltage ensures that the drive trips when the DC-link voltage is too low or too high.
• The drive is protected against ground faults on motor terminals U, V, W.
6.4.2 Mains Supply (L1, L2, L3)
Supply voltage 200–240 V ±10%
Supply voltage 380–480 V ±10%
Supply voltage 525–600 V ±10%
Supply frequency 50/60 Hz
Maximum imbalance temporary between mains phases 3.0% of rated supply voltage
True power factor (λ) ≥0.9 nominal at rated load
Displacement power factor (cosφ) near unity (>0.98)
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H1–H5, I2, I3, I4 Maximum 1 time/30 s
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H6–H10, I6–I8 Maximum 1 time/minute
Environment according to EN 60664-1 Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100000 A
rms
symmetrical Amperes, 240/480 V maximum.
6.4.3 Motor Output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency 0–400 Hz
Switching on output Unlimited
Ramp times 0.05–3600 s
6.4.4 Cable Length and Cross-section
Maximum motor cable length, shielded/armored (EMC-correct installation) See 6.2 EMC Emission Test Results.
Maximum motor cable length, unshielded/unarmoured 50 m (164 ft)
Maximum cross-section to motor, mains See 6.1.2 3x380–480 V AC for more information
Cross-section DC terminals for filter feedback on enclosure sizes H1–H3, I2, I3, I4
4 mm
2
/11 AWG
Cross-section DC terminals for filter feedback on enclosure sizes H4–H5
16 mm
2
/6 AWG
Maximum cross-section to control terminals, rigid wire
2.5 mm
2
/14 AWG
Maximum cross-section to control terminals, flexible cable
2.5 mm
2
/14 AWG