FC101 Programming Guide

Digital input
function
Description
[64] Counter B (down) Input for decrement counting in the SLC
counter.
[65] Reset Counter B Input for reset of counter B.
[101] Sleep A signal applied puts the frequency
converter into sleep mode.
Table 3.3 Digital Input Functions
Selected
preset
reference:
Preset
reference bit 2
Preset
reference bit 1
Preset
reference bit 0
Preset
reference 0
0 0 0
Preset
reference 1
0 0 1
Preset
reference 2
0 1 0
Preset
reference 3
0 1 1
Preset
reference 4
1 0 0
Preset
reference 5
1 0 1
Preset
reference 6
1 1 0
Preset
reference 7
1 1 1
Table 3.4 Selected Preset Reference
5-10 Terminal 18 Digital Input
Parameter for conguring the input function on input terminal
18. Refer to Table 3.3 for setting options.
Option: Function:
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8] * Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
5-10 Terminal 18 Digital Input
Parameter for conguring the input function on input terminal
18. Refer to Table 3.3 for setting options.
Option: Function:
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire Mode
[52] Run permissive
[53] Hand start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
[101] Sleep
[120] Lead Pump Start
[121] Lead Pump Alternation
[130] Pump 1 Interlock
[131] Pump 2 Interlock
[132] Pump 3 Interlock
[133] Pump 4 Interlock
[134] Pump 5 Interlock
5-11 Terminal 19 Digital Input
Parameter for conguring the input function on input terminal
19.
Option: Function:
[0] * No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire Mode
Parameters Programming Guide