FC101 Programming Guide
16-63 Terminal 54 Setting
View the setting of input terminal 54.
•
Current = 0
•
Voltage = 1
Option: Function:
[0] * Current mode
[1] Voltage mode
16-64 Analog input 54
Range: Function:
1* [0 - 20 ] View the actual value at input 54.
16-65 Analog output 42 [mA]
Range: Function:
0 mA* [0 - 20
mA]
View the actual value at output 42 in mA.
The value shown reects the selection in
parameter 6–90 Terminal 42 Mode and
parameter 6-91 Terminal 42 Analog Output.
16-66 Digital Output
Range: Function:
0* [0 -
15 ]
View the binary value of all digital outputs.
Denition:
X: Not used
0: Low
1: High
XX None used
X0 Terminal 42 not used, terminal 45
low.
X1 Terminal 42 not used, terminal 45
high.
0X Terminal 42 low, terminal 45 not
used.
0 Terminal 42 low, terminal 45 low.
1 Terminal 42 low, terminal 45 high.
1X Terminal 42 high, terminal 45 not
used.
10 Terminal 42 high, terminal 45 low.
11 Terminal 42 high, terminal 45 high.
Table 3.9 Binary Value of Digital Outputs
16-67 Pulse Input #29 [Hz]
Range: Function:
0* [0 - 130000 ] View the actual frequency rate on terminal 29.
16-71 Relay output
Range: Function:
0* [0 - 31 ] View the setting of the relay.
16-71 Relay output
Range: Function:
Bit 0~2 Unused
Bit 3 Relay 02
Bit 4 Relay 01
Bit 5~15 Unused
Table 3.10 Bits Denition
16-72 Counter A
Range: Function:
0* [-32768 -
32767 ]
View the present value of counter A. Counters are
useful as comparator operands, see
parameter 13-10 Comparator Operand.
The value can be reset or changed either via
digital inputs (parameter group 5-1* Digital Inputs)
or by using an SLC action (parameter 13-52 SL
Controller Action).
16-73 Counter B
Range: Function:
0* [-32768 -
32767 ]
View the present value of counter B. Counters are
useful as comparator operands
(parameter 13-10 Comparator Operand).
The value can be reset or changed either via
digital inputs (parameter group 5-1* Digital Inputs)
or by using an SLC action (parameter 13-52 SL
Controller Action).
16-79 Analog output 45 [mA]
Range: Function:
0 mA* [0 - 20
mA]
View the actual value at output 45 in mA.
The value shown reects the selection in
parameter 6-70 Terminal 45 Mode and
parameter 6-71 Terminal 45 Analog Output.
3.12.6 16-8* Fieldbus & FC Port
Parameters for reporting the bus references and control
words.
16-86 FC Port REF 1
Range: Function:
0* [-32768 - 32767 ] View the last received reference from the
FC port.