FC101 Programming Guide
3.11 Main Menu - Drive Information - Group
15
Parameter group containing frequency converter
information such as operating data, hardware congu-
ration, and software versions.
3.11.1 15-0* Operating Data
15-00 Operating hours
Range: Function:
0 h* [0 - 0x7f. h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is turned
o.
15-01 Running Hours
Range: Function:
0 h* [0 -
0x7f. h]
View how many hours the motor has run.
Reset the counter in parameter 15-07 Reset
Running Hours Counter. The value is saved
when the frequency converter is turned o.
15-02 kWh Counter
Range: Function:
0 kWh* [0 - 65535
kWh]
View the output power of the frequency
converter in kWh as a mean value over 1
hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range: Function:
0* [0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range: Function:
0* [0 - 65535 ] View the number of frequency converter
temperature faults that have occurred.
15-05 Over Volt's
Range: Function:
0* [0 - 65535 ] View the number of frequency converter
overvoltages that have occurred.
15-06 Reset kWh Counter
Option: Function:
NOTICE
To reset, press [OK].
[0] * Do not reset
15-06 Reset kWh Counter
Option: Function:
[1] Reset counter To reset the kWh counter to 0, select [1]
Reset and press [OK] (see
parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset
[1] Reset counter To reset the running hours counter, select [1]
Reset counter and press [OK]
(parameter 15-01 Running Hours) to 0 (see
also parameter 15-01 Running Hours).
3.11.2 15-3* Alarm Log
Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] the oldest. Fault codes, values, and time
stamp can be viewed for all logged data.
15-30 Alarm Log: Error Code
Range: Function:
0* [0 - 255 ] View the fault code and lookup its meaning in
chapter 4 Troubleshooting.
15-31 InternalFaultReason
Range: Function:
0* [-32767 - 32767 ] View a description of the error. This
parameter is used with alarm 38, Internal
Fault.
3.11.3 15-4* Drive Identication
Parameters containing read-only information about the
hardware and software conguration of the frequency
converter.
15-40 FC Type
Range: Function:
0* [0 - 6 ] View the FC type code. The readout is identical to
the frequency converter series power eld of the
type code denition, characters 1–6.
15-41 Power Section
Range: Function:
0* [0 - 20 ] View the FC type code. The readout is identical to
the frequency converter series power eld of the
type code denition, characters 7–10.
Parameters Programming Guide