Manual
Table Of Contents
- VLT® HVAC Basic Drive FC 101
- English US
- Contents
- Introduction
- Safety
- Installation
- Mechanical Installation
- Electrical Installation
- Electrical Installation in General
- IT Mains
- Mains and Motor Connection
- Introduction
- Connecting to Mains and Motor
- Relays and Terminals on Enclosure Sizes H1–H5
- Relays and Terminals on Enclosure Size H6
- Relays and Terminals on Enclosure Size H7
- Relays and Terminals on Enclosure Size H8
- Connecting to Mains and Motor for Enclosure Size H9
- Relays and Terminals on Enclosure Size H10
- Enclosure Size I2
- Enclosure Size I3
- Enclosure Size I4
- IP54 Enclosure Sizes I2, I3, I4
- Enclosure size I6
- Enclosure size I7, I8
- Fuses and Circuit Breakers
- EMC-correct Electrical Installation
- Control Terminals
- Electrical Wiring
- Acoustic Noise or Vibration
- Programming
- Warnings and Alarms
- Specifications
- Index
- English US
Parameter Range Default Usage
Parameter 1-45
q-axis Induc-
tance Sat.
(LqSat)
0.000–1000.000 mH Size related This parameter corresponds to the inductance saturation of
Lq. Ideally, this parameter has the same value as parameter
1-38 q-axis Inductance (Lq). However, if the motor supplier
provides an induction curve, enter the induction value, which
is 200% of the nominal current.
Parameter 1-46
Position Detec-
tion Gain
20–200% 100% Adjusts the height of the test pulse during position detection
at start.
Parameter 1-48
Current at Min
Inductance for
d-axis
20–200% 100% Enter the inductance saturation point.
Parameter 1-49
Current at Min
Inductance for
q-axis
20–200% 100% This parameter specifies the saturation curve of the d- and q-
inductance values. From 20–100% of this parameter, the in-
ductances are linearly approximated due to parameter 1-37 d-
axis Inductance (Ld), parameter 1-38 q-axis Inductance (Lq), pa-
rameter 1-44 d-axis Inductance Sat. (LdSat), and parameter 1-45
q-axis Inductance Sat. (LqSat).
Parameter 1-70
PM Start Mode
[0] Rotor Detection
[1] Parking
[0] Rotor De-
tection
Select the PM motor start mode.
Parameter 1-73
Flying Start
[0] Disabled
[1] Enabled
[0] Disabled Select [1] Enabled to enable the drive to catch a spinning mo-
tor in, for example, fan applications. When PM is selected, this
parameter is enabled.
Parameter 3-02
Minimum Ref-
erence
-4999.000–4999.000 0 The minimum reference is the lowest value obtainable by
summing all references.
Parameter 3-03
Maximum Ref-
erence
-4999.000–4999.000 50 The maximum reference is the highest value obtainable by
summing all references.
Parameter 3-10
Preset Refer-
ence
-100–100% 0 Enter the setpoint.
Parameter 3-41
Ramp 1 Ramp
Up Time
0.05–3600.0 s Size related Ramp-up time from 0 to rated parameter 1-23 Motor Frequen-
cy for asynchronous motors. Ramp-up time from 0 to parame-
ter 1-25 Motor Nominal Speed for PM motors.
Parameter 3-42
Ramp 1 Ramp
Down Time
0.05–3600.0 s Size related Ramp-down time from rated parameter 1-23 Motor Frequency
to 0 for asynchronous motors. Ramp-down time from param-
eter 1-25 Motor Nominal Speed to 0 for PM motors.
Parameter 4-12
Motor Speed
Low Limit [Hz]
0.0–400.0 Hz 0.0 Hz Enter the minimum limit for low speed.
Parameter 4-14
Motor Speed
High Limit [Hz]
0.0–400.0 Hz 100 Hz Enter the minimum limit for high speed.
Programming
Operating Guide | VLT® HVAC Basic Drive FC 101
AQ275641848264en-000101 / 132R0078| 53