| Electrical connection
8.3 Assembly tilting device (FTG)
Danger of injury by tilting the fan during installation.
The tilting device must be secured in the opened state
by screws in the designated hole against
unintentional folding.
Leaking duct system.
When installing the roof fan and accessories, all
mounting surfaces have to be sealed air tight.
1.
A
B
2. 3.
E
F
1:5
E
1:5
F
6.5 mm
A
B
9 Electrical connection
Safety information
Observe 2 Important safety information, page 1
Prevent the ingress of water into the connection box.
Connection
Check if the data on the nameplate matches the
connection data.
Complete the electrical connection according to the
circuit diagram.
Fans with EC- motors must be switched on/off via the
control input.
Connect the cable end in a dry environment.
Install a circuit breaker in the permanent electrical
installation, with a contact opening of at least 3 mm
at each pole.
Protective grounding wire
The protective grounding must have a cross-section equal to or greater than that of the phase conductor.
Residual current circuit breaker
All-current-sensitive residual current circuit breakers are required for use in alternating-current systems with 50/60
Hz, in combination with electronic devices such as EC motors, frequency converters or uninterruptible power supplies
(UPS).