MODBUS LITE V5.01 parameter specification
Table Of Contents
- 1 Frame protocol
- 2 Holding Register
- 2.1 Overview
- 2.2 Reset
- 2.3 Default set value
- 2.4 Password
- 2.5 Control default setting
- 2.6 Control customer setting
- 2.7 Operating hours counter
- 2.8 Operating minutes counter
- 2.9 Fan address
- 2.10 Source set value
- 2.11 Preferred running direction
- 2.12 Save set value
- 2.13 Internal parameter set
- 2.14 Control mode
- 2.15 Control parameters
- 2.16 Maximum modulation level
- 2.17 Minimum modulation level
- 2.18 Enable motor stop
- 2.19 Set value (EEPROM)
- 2.20 Starting modulation level
- 2.21 Maximum permissible modulation level
- 2.22 Minimum permissible modulation level
- 2.23 Maximum speed
- 2.24 Maximum permissible speed
- 2.25 Ramp-up curve / ramp-down curve
- 2.26 Limit speed
- 2.27 Potentiometer characteristic
- 2.28 Control limitation
- 2.29 Maximum power
- 2.30 Maximum coil current
- 2.31 Limiting speed for running monitor
- 2.32 Interface settings
- 2.33 Shedding function
- 2.34 Relay dropout delay
- 2.35 Fail safe function on/off
- 2.36 Fail safe function set value
- 2.37 Fail safe function time lag
- 2.38 Fail safe function running direction
- 2.39 Potentiometer characteristic limiting value for cable break
- 2.40 Sensor
- 2.41 Customer data
- 2.42 Error history
- 2.43 Reference value of DC-link voltage
- 2.44 Reference value of DC-link current
- 2.45 Production data
- 3 Input Register
- 3.1 Overview
- 3.2 Identification
- 3.3 Maximum number of bytes
- 3.4 Software name of bus controller
- 3.5 Software version of bus controller
- 3.6 Software name of commutation controller
- 3.7 Software version of commutation controller
- 3.8 Actual speed
- 3.9 Motor status
- 3.10 Warning
- 3.11 DC-link voltage
- 3.12 DC-link current
- 3.13 Module temperature
- 3.14 Motor temperature
- 3.15 Interior electronics temperature
- 3.16 Current direction of rotation
- 3.17 Current modulation level
- 3.18 Current set value
- 3.19 Sensor actual values
- 3.20 Current parameter set
- 3.21 Current power
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 18 of 70
Form 1003
1.3.6.3 Write Single Register Addressed By Serial No.
Command code: 0x46
This command is used to write the content of one holding register.
In contrast to "MODBUS over Serial Line Specification & Implementation Guide V1.0", the fan also responds
to a broadcast command (MODBUS address = 0), provided that no broadcast identifier (0) is used in the serial
number. Because no two different fans can have the same serial number, it is not possible for more than one
fan to respond.
Command from master:
10 data bytes are transmitted:
Serial No. byte 1
Serial No. byte 2
Serial No. byte 3
Serial No. byte 4
Serial No. byte 5
Serial No. byte 6
MSB holding register address
LSB holding register address
MSB data to be written
LSB data to be written
The holding registers are described below.
Response from fan:
10 data bytes are transmitted:
Serial No. byte 1
Serial No. byte 2
Serial No. byte 3
Serial No. byte 4
Serial No. byte 5
Serial No. byte 6
MSB holding register address
LSB holding register address
MSB data to be written
LSB data to be written
The command from the master is repeated in the response.
Exception codes:
In case of error, only one data byte (the exception code) will be transmitted
Exception codes:
0x02: Permissible range of the holding registers 0xD000 to 0xD3FF exceeded.
0x04: There is no write access in this authorisation level (password).