Fire Safety Products FGS Air Transfer Grille Data Sheet
Table of Contents Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Highlights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Product Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Design . . . . . . . . . . . . . . . . . . . . . .
Rectangular Fire Dampers | 1/8 Description Air transfer grille FGS - type MMS represent passive fire protection, designed with the help of compartmentalization to prevent the spread of toxic gases, smoke and fire. FGS - fire resistant and cold smoke control mechanical air transfer grille (type MMS) are designed and certified in accordance with EN 1364-1 and ETAG 026 part 4, classified according to EN 13501-2.
2/8 | Rectangular Fire Dampers Design Material Composition The product contains galvanized sheet metal, calciumsilicate board, fireproof carbon fiberglass, polyurethanwe foam and ethylene - propylene rubber. These are processed in accordance with local regulations. The product contains no hazardous substances, with the exception of the solder in the thermofuse, which contains a milligram of lead.
Rectangular Fire Dampers | 3/8 Fire Resistivity The FGS - Cold smoke control and fire resistant mechanical air transfer grille, type MMS has been tested in accordance to EN 1364-1:2015. The FGS is classified in accordance to EN 13501-2:2016. Cold smoke leakage has been tested in accordance with EN 1634-3:2004/AC:2006 and classified as Sa = 238 m3/(h · m2) at 25 Pa according to EN 1364-5:2017 and ETAG 026 Part 4. Tab.
4/8 | Rectangular Fire Dampers Tab.
Rectangular Fire Dampers | 5/8 Ordering Code FGSDimensions 1) L×H Type of Activation 2) ZV DV1 DV1-2 DV7-T DV9-T DV9-T-ST Grille Surface Finish 3) RALXXXX NOTES: 1) Dimensions L × H: nominal dimensions of the air transfer grille (Length × Height in mm) 2) Type of activation: see details on page 2. 3) If no surface finish is defined, the grille will be delivered galvanised as standard. On demand delivery of the FGS with perforated plates is done for aesthetic reasons.
6/8 | Rectangular Fire Dampers Technical Parameters Durability test 250/1000 cycles Leakage Sa = 238 m3/(h · m2 *) at 25 Pa Safe position Closed Possible installations In the wall only (see Tab. 1) Airflow direction Both directions Allowed air velocity Max.
Rectangular Fire Dampers | 7/8 Installation, Maintenance & Operation Information about installation, maintenance and operation is available in the document “UserManual_FGS”. FGS air transfer grille is maintenance free. The FGS is designed to be situated only in internal conditions with humidity lower than 85% RH where the operating temperatures do not fall below 0 °C and installed in vertical supporting construction.
8/8 | Rectangular Fire Dampers Related Products PKIR3G, PKIS3G, PKIS3GA, PKIS EI90S, PKIS EI120S Fire Dampers Product information is available within the technical documentation “DataSheet_PKIR_PKIS” or at Systemair DESIGN. 1396 - CPD - 0062 1396 - CPR - 0076 1396 - CPD - 0061 1396 - CPR - 0077 PKI-C Cartridge Fire Damper Product information is available within the technical documentation “DataSheet_PKI-C” or at Systemair DESIGN.