Controller Setup OFF Value Group4
Switch-off value for group4
Setting range: 0 - 100 %
Factory setting: 80 % *
80 %
OFF Value Group4
Controller Setup nmin at Group4
Minimum Value for Group4
Setting range: 0 - 100 %
Factory setting: 40 % *
40 %
nmin at Group4
* Display as long as no group assignment via analogue output, relay, MODBUS:
|
- - - -
|
Higher settings must be selected for following groups and the switch-off value of the group must be
below the switch-on value.
Example version 0 via MODBUS
On controlled group and three switched groups
UNIcon
MODBUS Master
Signal
Controller
Slave
G1
M
Analog
In
MODBUS
2A
1A (1D+), 1B (D-)
5A
0...100 %
Controller
Slave
G2
M
0 / 100 %
11.09.2014
v_group_var_4_dig_out_cxe_master.vsd
A (D+)
B (D-)
A (D+)
B (D-)
11A
12A
Controller
Slave
G4
M
0 / 100 %
Controller
Slave
G3
M
0 / 100 %
A (D+)
B (D-)
A (D+)
B (D-)
11.09.2014
v_cxe_4_group_digswitch_dia.vsd
80
70
60
50
40
30
20
10
10 20
30
40 50 60
70 80 90
100
0...100 %
0
90
100
G2 ON @ 50 %
nmin @
G3= 30 %
nmin @
G2= 20 %
G2 OFF
nmin @
G4= 40 %
G3 OFF
G4 OFF
G3 ON @ 70 %
G4 ON @ 85 %
MODBUS Out [%]
MODBUS Out
2A = Standard
S
G1 2A
MODBUS Out: speed setting over MODBUS
S: Modulation level of the controller in %
G1: Group 1
G2: Group 2
G3: Group 3
G4: Group 4
G2, G3, G4 ON: ON Value Group2, 3, 4
G2, G3, G4, OFF: OFF Value Group2, 3, 4
nmin@G 2, 3, 4: nmin at Group2, 3, 4
MODBUS Out Standard: Diagram wihout group control
Function
Group 1 is continuously controlled (0 - 100 %), the other groups are switched on and off depending on
the degree of modulation (0 / 100%).
If the modulation level exceeds the switch-on point ON Value Group2, the MODBUS Master switches
on the second group and the speed of the rst group is reduced to an adjustable minimal value nmin
at Group2.
Then the speed of the rst group increases to maximum within the remaining range.
If a third group is programmed up to switch-on point ON Value Group3 etc.
Switch-off point OFF Value Group2 at diminishing speed requirement.
Operating Instructions POC-M Programming