L BAL E234 GB MANUAL

Table Of Contents
Information
By entering the PIN 9095 in the PIN menu of the Start menu group the device is reset to the as-
delivered state (except for the saved events in the Protocolmenu).
Any changes that have been made to the settings are thus lost.
9.4.4 Sensor Alarm ON / OFF
The inputs E1 Analogue In and if Sensor 2 is activated E2 Analogue In are monitored.
In case of an interruption or short-circuit in the sensor conductor, or in case of measured values that
lie outside of the devices measurement range, a time-delayed fault indication takes place.
Function only in controller mode (from
2.01 )!
Controller Setup With Alarm Sensors = ON (factory setting). Indicated
sensor disturbances are displayed as Alarm alternating to
the actual value and stored in the menu of Protocol.
A programmed alarm relay (factory setting relay K2) indicates
the sensor failure.
Sensor 1
ON
Alarm sensors
Controller Setup With AlarmSensors = OFF areindicated sensor disturban-
ces as Message alternating to the actual value and stored in
the menu of Protocol.
Sensor 1
OFF
Alarm sensors
9.4.5 Limit
Controller Setup After allocation of a digital input (
IO Setup) an adjustable limitation of the modulation
can be activated via a digital input (D1, D2, ..).
Display as long as no allocation has been carried out in IO Setup:
|
- - - -
|
The limitation inuences both outputs in operation with two control circuits.
- - - - -
Limit
Limit value = max. possible modulation (e.g.
speed reduction during night operation by
time switch).
Setting range: Limit = Min. Speed to Max.
Speed.
Factory setting: 100 %
max. modulation, i.
e. no limit.
Setting depending on device tye in: % or rpm.
D
P
Min.
L= 70% Min.= 0 % Max. = 100 %
50 %
R
0 %
I
S
100 %
I
L
L = 70% Min. = 35 % Max. = 85 %
28.03.2013
v_limit_cxe_master.vsd
80
70
60
50
40
30
20
10
90
Analog Out [V]
1 2
3
4 5
6
7 8
9
10
MODBUS Out [%]
100
Limit (idealized principle diagram)
MODBUS Out: speed setting over MODBUS
Analog Out: speed setting over analog output 0 - 10 V
L Limit
S Setpoint
R Pband
D Speed controller: setting signal
P P-controller: control deviation
Operating Instructions POC-M Programming
L-BAL-E234-GB 1614 Index 002 Part.-No.
30/84