L BAL E234 GB MANUAL

Table Of Contents
IO Setup If the digital inputs have the same function allocation (also applies for timer function)
you can choose between an AND and OR operation.
OR operation (factory setting). The function becomes active when one of the digital
inputs or the timer is activated.
AND operation. The function becomes active when all digital inputs or also the timer
are activated.
OG
D - D Relation
Function Description
OFF No function (factory setting for D2)
Enable
(1D)
Enable (remote control) ON / OFF
External error
(2D)
External fault alarm
Limit
(3D)
Limit ON / OFF
Inuences control circuit 1 and control circuit 2 in operation with two control circuits
E1 / E2
(4D)
Switch over input E1 / E2 (for operation with one control circuit)
Setpoint1/2
(5D)
Switch over Setpoint 1 / Setpoint 2 für control circuit 1 (factory Setting for D1)
Setpoint int./ext.
(6D)
Switch over Intern / Extern
Possible only for operation with one control circuit!
Control/Manual
(7D)
Switch over automatic control / Speed manual
Possible only for operation with one control circuit!
Heating/Cooling
(8D)
Switch over control function (e.g. heating / cooling)
Reset
(10D)
Complete re-start of the device
Max. Speed
(11D)
Setting Max. Speed ON / OFF
Inuences the respectively set value 1. Max. Speed and 2. Max. Speed in operation
with two control circuits.
1.Setp+Pband1/2
(15D)
for control circuit 1: Switch over Setpoint 1/2 and Pband 1/1
When programming this function, Setting additionally lists the parameter: 1.Pband2
for control circuit 1.
Override Time
(21D)
Overwrite timer function (in operation with timer)
The timer output is overwritten for a settable time with a selectable status (ON / OFF).
Only active in operation with a second control circuit
E1 / E2
(4D)
The output for control circuit 2 is set additionally to A2 to A1 (regardless of the
programmed function for A1). Control circuit 1 has no output for the duration of the
switching.
The switch over input E1 / E2 as in operation with one control circuit is no longer
possible.
2. Setpoint 1/2
(9D)
for control circuit 2: Switch over 2. Setpoint 1 / 2. Setpoint 2
2.Setp+Pband1/2
(16D)
for control circuit 2: Switch over Setpoint 1/2 and Pband 1/2
When programming this function, Setting additionally lists the parameter: 2Pband2
for control circuit 2.
Operating Instructions POC-M Programming
L-BAL-E234-GB 1614 Index 002 Part.-No.
41/84