6.3 External Setpoint / External speed setting in manual operation
External setpoint setting or external manual operation are possible using a 0 - 10 V (0 - 20 mA, 4 - 20 mA) signal
at the E2 and GND terminals. Congure E2 in Base setup. For potentiometers, program Analog Out 1
(terminal A1) to the function
|
1A
|
= +10 V (as factory setting
IO Setup).
E2 Analog In = factory setting 0 - 10 V
18.03.2013
v_extern_pot@a2.vsd
0 - 10 V
0 - 10 V
10 k
A2
GND
E2
GND
External Setpoint via external signal instead of Setpoint 1. The external Setpoint function must be activated
in base setup
|
1E
|
for E3 function. The active external Setpoint value is displayed in the info menu group.
External speed setting in manual operation. The external manual operation function must be activated in the
basic settings
|
2E
|
for E3 function. Switchover between settings on the device and external manual operation
via the digital input (
IO Setup: Control / manual operation
|
7D
|
).
Not possible in modes with 2 sensors and operation with a second control circuit because the second
analogue input is already occupied by it.
7 Start-up
7.1 Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. Make sure that no persons or objects are in the fan's hazardous area.
Operating Instructions POC-M Start-up
L-BAL-E234-GB 1614 Index 002 Part.-No.
18/84