9.7 Timer
9.7.1 Timerfunction
The device has a real time clock. The clock is backed up (Gold Cap) and has a reserve of 2 or 3 days
after sufcient operation on a voltage supply.
The time and date must be set during start-up operation and when using the real-time clock. The
device calculates the weekday based on the date.
In principle, the timer function acts like a digital switch input (timer On
closed contact at inverting
OFF). The same functions can be assigned to the timer switch as the digital inputs(D1 ..D2).
Function Description * Timer ON =
(@ Timer Invert. = OFF)
OFF no function (factory setting)
Enable
(1D)
Enable (remote control) ON / OFF
Device ON
External error
(2D)
External fault alarm
Fault
Limit
(3D)
Limit ON / OFF
Inuences control circuit 1 and control circuit 2 in operation
with two control circuits
Limit ON
E1 / E2
(4D)
Switch over input E1 / E2 (for operation with one control
circuit)
Signal at E2
Reset
(10D)
Complete re-start of the device
Reset
Max. Speed
(11D)
Setting Max. Speed ON / OFF
Inuences the respectively set value 1. Max. Speed and 2.
Max. Speed in operation with two control circuits.
Max. Speed ON
Override Time
(21D)
Do not use function for timer (only for digital input).
-
For mode speed controller 1.01
Setpoint1/2
(5D)
Switch over Set Intern1 / Set Intern2
Setting External 1 must be at OFF.
Set Intern2
Setpoint int./ext.
(6D)
Switch over Intern / Extern
Set extern
For modes as controller (from 2.01. )
Setpoint1/2
(5D)
Switch over Setpoint 1 / Setpoint 2for control circuit1
Setpoint2
Setpoint int./ext.
(6D)
Switch over Intern / Extern
Possible only for operation with one control circuit!
Setpoint External
Control/Manual
(7D)
Switch over automatic control / Speed manual
Possible only for operation with one control circuit!
Manual mode
Heating/Cooling
(8D)
Switch over control function (e.g. heating / cooling)
Reversal standard
1.Setp+Pband1/2
(15D)
for control circuit 1: Switch over Setpoint 1/2 and Pband 1/1
When programming this function, Setting additionally lists
the parameter: 1.Pband2 for control circuit 1.
First control circuit Set-
point 2 + Pband 2
Only active in operation with a second control circuit
E1 / E2
(4D)
The output for control circuit 2 is additionally set to A2 to
A1 (regardless of the programmed function for A1). The
rst control circuit has no output for the duration of the switch
over.
The switch over input E1 / E2 as in operation with one
control circuit is no longer possible.
Second control circuit to
A1 + A2
Operating Instructions POC-M Programming
L-BAL-E234-GB 1614 Index 002 Part.-No.
58/84