L BAL E234 GB MANUAL
Table Of Contents
- 1 General notes
- 2 Safety instructions
- 2.1 Intended use
- 2.2 Explanations of symbols
- 2.3 Product safety
- 2.3 Product safety
- 2.4 Requirements placed on the personnel / due diligence
- 2.4 Requirements placed on the personnel / due diligence
- 2.5 Start–up and during operation
- 2.5 Start–up and during operation
- 2.6 Work on the device
- 2.6 Work on the device
- 2.7 Modifications / interventions in the device
- 2.7 Modifications / interventions in the device
- 2.8 Operator’s obligation of diligence
- 2.8 Operator’s obligation of diligence
- 2.9 Employment of external personnel
- 2.9 Employment of external personnel
- 3 Product overview
- 3 Product overview
- 4 Mounting
- 4 Mounting
- 4.1 General notes
- 4.1 General notes
- 4.2 Connection pressure measuring tube
- 4.2 Connection pressure measuring tube
- 4.3 Outdoor installation
- 4.3 Outdoor installation
- 4.4 Installation location for agriculture
- 4.4 Installation location for agriculture
- 4.5 Temperature influences during commissioning
- 4.5 Temperature influences during commissioning
- 5 Electrical installation
- 5 Electrical installation
- 5.1 Safety precautions
- 5.1 Safety precautions
- 5.2 EMC–compatible installation of control lines
- 5.2 EMC–compatible installation of control lines
- 5.3 Mains connection
- 5.3 Mains connection
- 5.4 Signal input or sensor connection (E2)
- 5.4 Signal input or sensor connection (E2)
- 5.5 Control outputs 0 – 10V (A1, A2)
- 5.5 Control outputs 0 – 10V (A1, A2)
- 5.6 Voltage supply for external devices (+, GND)
- 5.6 Voltage supply for external devices (+, GND)
- 5.7 Digital inputs (D1, D2)
- 5.7 Digital inputs (D1, D2)
- 5.8 Relay outputs
- 5.8 Relay outputs
- 5.9 RS–485 interfaces for MODBUS RTU
- 5.9 RS–485 interfaces for MODBUS RTU
- 5.10 USB–interface
- 5.10 USB–interface
- 5.11 Potential at control voltage connections
- 5.11 Potential at control voltage connections
- 6 Select operation mode
- 6 Select operation mode
- 7 Start–up
- 8 Controls and Menu
- 9 Programming
- 9.1 Pressure control airconditioning
- 9.2 Menu group Start
- 9.3 Menu group Info
- 9.4 Controller Setup
- 9.4.1 PIN protection
- 9.4.2 PIN protection
- 9.4.3 user settings
- 9.4.4 Sensor Alarm ON / OFF
- 9.4.5 Limit
- 9.4.6 Minimum speed cut off
- 9.4.7 Reverse action of the control function
- 9.4.8 Controller configuration
- 9.4.9 Group control
- 9.4.10 Display text for external message
- 9.4.11 Offset control signal
- 9.4.12 Selection amplifier (comparator) control circuit 1 or 2 at output A1
- 9.4.13 Data on the total control deviation
- 9.5 IO Setup
- 9.5.1 Analog outputs
- 9.5.2 Digital inputs
- 9.5.2.1 Menu overview
- 9.5.2.2 Enable
- 9.5.2.3 External message, Function
- 9.5.2.4 Limit ON / OFF, Function
- 9.5.2.5 Switch over input
- 9.5.2.6 Output control circuit 2 additional to
- 9.5.2.7 Set 1/2 or Setpoint 1/2, Function
- 9.5.2.8 Intern / Extern Function
- 9.5.2.9 Automatic control / speed manual Function
- 9.5.2.10 Reverse action of control function (
- 9.5.2.11 Switch over Setpoint 1/2 for control circuit 2
- 9.5.2.12 Setting Max. Speed ON / OFF function
- 9.5.2.13 Switch over Setpoint 1/2 and Pband 1/ 2 for control circuit 1
- 9.5.2.14 Switch over Setpoint 1/2 and Pband 1/2 for control circuit 2
- 9.5.2.15 Timer function overwrite
- 9.5.3 Configuration of analog inputs
- 9.5.4 Function and inverting for relay outputs
- 9.5.5 COM2
- 9.6 Limits
- 9.7 Timer
- 9.8 MODBUS Slave
- 9.9 MODBUS Master
- 9.10 Member MOBUS Master
- 10 Menu tables
- 10
- 11 Diagnostics menu
- 12 Protocol
- 13 Enclosure
9.7 Timer
9.7.1 Timerfunction
The device has a real time clock. The clock is backed up (Gold Cap) and has a reserve of 2 or 3 days
after sufficient operation on a voltage supply.
The time and date must be set during start-up operation and when using the real-time clock. The
device calculates the weekday based on the date.
In principle, the timer function acts like a digital switch input (timer “On”
closed contact at inverting
OFF). The same functions can be assigned to the timer switch as the digital inputs(“D1 ..D2)”.
Function Description * Timer ON =
(@ Timer Invert. = OFF)
OFF no function (factory setting)
Enable
(1D)
Enable (remote control) “ON” / “OFF”
Device ON
External error
(2D)
External fault alarm
Fault
Limit
(3D)
“Limit” ON / OFF
Influences control circuit 1 and control circuit 2 in operation
with two control circuits
Limit ON
E1 / E2
(4D)
Switch over input “E1” / “E2” (for operation with one control
circuit)
Signal at E2
Reset
(10D)
Complete re-start of the device
Reset
Max. Speed
(11D)
Setting Max. Speed “ON” / “OFF”
Influences the respectively set value “1. Max. Speed” and “2.
Max. Speed” in operation with two control circuits.
Max. Speed ON
Override Time
(21D)
Do not use function for timer (only for digital input).
-
For mode speed controller 1.01
Setpoint1/2
(5D)
Switch over “Set Intern1” / “Set Intern2”
“Setting External 1” must be at “OFF”.
Set Intern2
Setpoint int./ext.
(6D)
Switch over “Intern” / “Extern”
Set extern
For modes as controller (from 2.01. )
Setpoint1/2
(5D)
Switch over “Setpoint 1” / “Setpoint 2”for control circuit1
Setpoint2
Setpoint int./ext.
(6D)
Switch over “Intern” / “Extern”
Possible only for operation with one control circuit!
Setpoint External
Control/Manual
(7D)
Switch over “automatic control” / “Speed manual”
Possible only for operation with one control circuit!
Manual mode
Heating/Cooling
(8D)
Switch over control function (e.g. “heating” / “cooling”)
Reversal standard
1.Setp+Pband1/2
(15D)
for control circuit 1: Switch over Setpoint 1/2 and Pband 1/1
When programming this function, “Setting” additionally lists
the parameter: “1.Pband2 for control circuit 1.”
First control circuit Set-
point 2 + Pband 2
Only active in operation with a second control circuit
E1 / E2
(4D)
The output for control circuit 2 is additionally set to “A2” to
“A1” (regardless of the programmed function for “ A1”). The
first control circuit has no output for the duration of the switch
over.
The switch over input “E1” / “E2” as in operation with one
control circuit is no longer possible.
Second control circuit to
A1 + A2
Operating Instructions POC-M Programming
L-BAL-E234-GB 1614 Index 002 Part.-No.
58/84