For operation as controller (starting from 2.01 ): switch over Setpoint 1 / external Setpoint
Possible only for operation with one control circuit!
Under Base setup E2 function programmed to function
|
1E
|
for external setpoint .
Contact at digital input e.g. Digital In 1 = D1 - D1
Controller
24V
D1 D1
10
n = 0 – 100 %
- - - - -
Se
ES E2
26.05.2010
v_6d_sollwert1_externer_sollwert.vsd
1
1 Setting Setpoint1
ES External Setpoint e.g. 5 V
23.8°C
Se Sensor
D1 Inverting = ON: Setting at the unit at
opened contact / Signal Extern at closed
contact
D1 Inverting = OFF: Setting at the unit at
closed contact / Signal Extern at opened
contact
9.5.2.9 Automatic control / speed manual Function
|
7D
|
(mode 2.01 )
Possible only for operation with one control circuit!
Switch over between automatic control to set target value (depending on the activation: Setpoint1,
Setpoint2) and the default for manual operation set at the device.
If for Analog In 2 E2 function is programmed to
|
2E
|
switch over between Setpoint1 or Setpoint2
and external manual operation. With activated manual mode the display constantly changes between
actual value and value for manual mode.
Contact at digital input e.g. Digital In 1
Controller
24V
D1 D1
10
n = 0 -100 %
1
n = 80 %
0
- - - - -
- - - - -
- - - - -
Se
E1
ES E2
26.05.2010
v_7d_regelung_hand.vsd
3
2
1
1 Setting Setpoint1
2 Setting Setpoint2
3 Setting Speed manual (depending on device type in: %, Hz, rpm)
EH Signal for Manual mode extern, E2 Function =
|
2E
|
Se Sensor
D1 Inverting = OFF Automatic control at
opened contact / manual operation at closed
contact.
D1 Inverting = ON: Automatic control at
closed contact / manual operation at opened
contact.
9.5.2.10 Reverse action of control function (
2.01 ), Function
|
8D
|
Switchover between: Increasing modulation during increasing actual-value and increasing modulation
during sinking actual-value.
The factory presets for the Control function are dependent on the selected mode of operation (
Controller Setup - reverse operation of the control function).
When switching over via a digital input, the device works with the opposite function as set there.
The inversion of the control function inuences both circuits in operation with two control circuits.
Controller Setup Settings in Controller Setup
Display for operation with two control circuits:
1. Actual>Set=n for control circuit 1
2. Actual>Set=n for control circuit 2
ON
Val>Set=n+
Operating Instructions POC-M Programming
L-BAL-E234-GB 1614 Index 002 Part.-No.