L BAL E234 GB MANUAL

Table Of Contents
Info
Operation with Set Intern2 is signalized by the moon symbol for reduced operation.
Set extern1 under settings must be programmed to OFF.
50 %
Modulation
For operation as controller (starting from 2.01 ): switch over Setpoint 1 / Setpoint 2
For operation with second control circuit: switch over 1.Setpoint 1 / 1.Setpoint 2
Contact e.g. at ditgital input Digital In 1 (depending on device type at terminals D1 - D1or D1 -
24 V).
Controller
10
n = 0 – 100 %
- - - - -
- - - - -
Sensor
11.05.2007
v_5d_sollwert_1_2.vsd
2
1
24V
D1 D1
1 Setting Setpoint 1 or 1.Setpoint 1 (display in operation with two
control circuits for Setpoint 1 of control circuit 1)
2 Setting Setpoint 2 or 1.Setpoint 2 (display in operation with two
control circuits for Setpoint 2 of control circuit 1)
D1 Inverting = OFF: Setpoint1 = 18 °C
at opened contact / Setpoint2 = 25 °C at
closed contact.
D1 Inverting = ON: Setpoint1 = 18 °C
at closed contact / Setpoint2 = 25 °C at
opened contact.
Info
Operation with Setpoint2 is signalized by the moon symbol for reduced operation.
28.7 °C
E1 Actual
9.5.2.8 Intern / Extern Function
|
6D
|
For Mode Speed controller 1.01 : Switch over Set Intern / Set external
Set extern1 under settings must be programmed to OFF.
Contact e.g. at ditgital input Digital In 1 (depending on device type at terminals D1 - D1or D1 -
24 V).
Controller
24V
D1 D1
10
n = 40 %
n = 80 %
Si 40 %
- - - - -
E1
11.05.2007
v_6d_vorgabe_intern_extern.vsd
1
0
1
Si Signal
1 Setting Set Intern1 (depending on device type in: %, Hz, rpm)
D1 Inverting = OFF: Set Intern1 at
opened contact / Setting Extern at closed
contact.
D1 Inverting = ON: Set Intern1 at
closed contact / Set Extern at opened
contact.
Operating Instructions POC-M Programming
L-BAL-E234-GB 1614 Index 002 Part.-No.
44/84