L BAL E231 GB QUICK START

8.2 Connection diagram
1 Line
2 Digital inputs for potential-free contacts, D1 pre-programmed for switch over setpoint 1/2
3 Outputs (I
max
= 2 mA): A1 pre-programmed control output e.g. for controlling a speed controller. Fans with integrated controller and input 0 -
10 V can be activated directly. A2 pre-programmed for constant voltage +10 V
4 Outdoor temperature sensor to E2: TF.. (KTY, Pt1000), alternatively 0...10 V, 0...20 mA, 4...20 mA,
5 Internal pressure sensor to E1
6 Jumper J1 for USB interface (Bootloader)
7 Contact rating max. AC 250 V 2 A (ohmic load)
Attention!
Plug the jumper J1 to both PINs only for a software update via USB interface. The device will not switch on if this jumper is
plugged to both PINs!
Do not replug the jumper under voltage, observe the safety instructions!
8.3 Dimensions [mm]
Quick Start Guide POC-M Enclosure
L-BAL-E231-GB 1446 Index 001 Part.-No. 00163429-42
14/15