Modbus Registers OPTIMA...BLC1MOD

VAV-Compact
Volumetric flow compact control device
6 VAV-Compact Modbus Register • en-gb • 2019-03 • Subject to changes www.belimo.com
Modbus Register Description
No. Address Description
Comment
Range
Enumeration
Unit Scaling Access
111 110 Nominal volumetric flow m
3
/h 1 R
112 111
113 112
Nominal volumetric flow
Vnom in unit selected (Register 118) LowWord
Lower 16 bit of 32 bit value
UnitSel 0.001 R
114 113 Nominal volumetric flow
Vnom in unit selected (Register 118) HighWord
Upper 16 bit of 32 bit value
115 114
116 115
117 116 Control Mode 0: Position control
1: Flow control
R / W
118 117 Unit Selection Flow 0: m
3
/s
1: m
3
/h
2: l/s
3: l/min
4: l/h
5: gpm
6: cfm
Default: m
3
/h(1)
R / W
119 118 Setpoint Source
Analog: Setpoint from analog signal 0 ... 10 V on wire 3
Bus: Setpoint from Modbus (Register 1)
0: Analog
1: Bus
Default: Bus(1)
R / W