Roof fans DVN(I), DVS(I), DVC(I), DHS, DHA Installation and Operating Instructions Document in original language | · 008 GB
© Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Contents 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 General information .........................................1 1.1 Warning symbols ...................................1 1.1.1 Instruction symbols.....................1 Important safety information .............................1 2.1 Personnel .............................................1 2.2 Personal protective equipment..................2 2.3 5 rules of electrical safety ........................2 Warranty ..............................................
General information | 1 General information 1.1 Warning symbols Note: Useful information and instructions 1.1.1 Instruction symbols Instruction Instruction with fixed sequence ♦ Carry out this action 1. Carry out this action ♦ (if applicable, further actions) 2 3. (if applicable, further actions) 2. Carry out this action Important safety information Planners, plant builders and operators are responsible for the proper assembly and intended use.
2 | Warranty Table 1 Qualifications Activities Qualifications Storage, operation, transport, cleaning, disposal Trained personnel (see following note) Electrical connection, commissioning, electrical disconnection Electrical expert or matching qualification Installation, disassembly Fitter or matching qualification Maintenance Electrical expert or matching qualification Fitter or matching qualification Electrical expert or matching qualification Fitter or matching qualification Repair Smoke e
Description | Unpacking When opening the transport packaging, there is a risk of damage from sharp edges, nails, staples, splinters etc. ♦ Unpack the fan carefully. ♦ Check the fan for obvious transport damage. ♦ Only remove the packaging shortly before assembly. Transport Safety information Warning: Electrical or mechanical hazards due to fire, moisture, short circuit or malfunction. ♦ Never transport the fan by the connecting wire, terminal box, impeller, protection grille, inlet cone or silencer.
| Description Incorrect use Incorrect use refers mainly to using the fan in another way to that described. The following examples are incorrect and hazardous: • Conveying of explosive and combustible media • Operation without duct system or protection grille • Conveying of aggressive media • Operation with the air connections closed • Operation in an explosive atmosphere 5.2 Technical data Max. ambient temperature [°C] Max.
Description | 5.
| Description 5.5 Description DVC/DVCI S-Version: The DVC-S version can be stepless controlled via a 0-10 V signal. The operating point can be directly adjusted with the integrated potentiometer (10 K ohms). POC-Version The DVC-POC version has integrated pressure sensors and temperature sensor for outdoor temperature compensation.
Description | Table 9 Dimensions DVC-P/DVC-POC A B F M20x1,5 K D C H I E A B C D E F H K I 190–225 370 320 175 - 335 245 6xM6 213 10 (4x) 315 560 470 330 378 435 330 6xM8 285 10 (4x) 355–400 723 623 390 438 595 450 6xM8 438 12 (4x) 450–500 900 730 465 515 665 535 6xM8 438 12 (4x) 560–630 1150 960 565 585 939 750 8xM8 605 14(4x) [mm] Table 10 Dimensions DVCI-P/DVCI-POC A B C D E F H K I 225 498 438 210 - 335 245 6xM6 213 10(4
8 | Description 5.6 Description DHS The fans are equipped with AC motors. For information on speed regulation options, see 6 Name plate and type key, page 9.
Name plate and type key | 6 Name plate and type key 1 8 2 3 4 5 6 7 1 Type designation 5 Enclosure class/fan impeller speed/weight 2 Voltage/current/frequency 6 Insulation class 3 Input power 7 Article number/production number/manufacturing date 4 Max.
10 | Accessories 7 Accessories For details of the accessories, please check our online catalog or contact Systemair.
11 Installation | 8 Installation Safety information ♦ Observe 2 Important safety information, page 1 ♦ Use installation material with fire resistance classes that meet temperature requirements. ♦ Provide contact and intake protection and ensure safety distances according to DIN EN ISO13857 and DIN 24167-1. ♦ To reduce transmission of vibration to the duct system, we recommend flexible connections from our accessory range, see chapter Accessories.
12 | Installation 8.1.1 DVC-P measuring tubes The following illustrations show the schematic installation of the measuring tubes. Size 190–225 Size 315–710 A Measuring tubes B Duct system Controller input A - Duct system + Atmosphere A B 8.2 B Assembly/Disassembly impeller — Internal rotor motor If an external rotor motor is used, the motor and impeller can`t be seperated. Damage to the motor and impeller.
Installation | The hub is shown without impeller due to better lucidity. Disassembly 1. Aluminium hub 2. 1. Steel hub 3. 4. 1. 1. 2. 2. Assembly 1. 2. 3. 4. 5. Aluminium hub Use screw locking The set screw must push on the wedge of the shaft. = Use screw locking 2. 1. 5. Steel hub 6. Steel hub Tighten the screws slightly Tighten the two screws evenly with the tightening torque according to table 15.
14 | Electrical connection 8.3 Assembly tilting device (FTG) Danger of injury by tilting the fan during installation. Leaking duct system. ♦ The tilting device must be secured in the opened state by screws in the designated hole against unintentional folding. ♦ When installing the roof fan and accessories, all mounting surfaces have to be sealed air tight. 1. 2. 3. 6.
Electrical connection | 9.1 Electrical connection accessories The following wiring diagrams show the electrical connections between accessories and fans (with EC motor) or frequency converters (e.g. FRQ, FRQS, FXDM) which can be controlled with a 0–10V signal. If you are not sure if your fan is equipped with an EC- motor please see chapter 6 Name plate and type key, page 9. motor/frequency converter 10V All fans with EC motors are equipped with a pre-wired potentiometer (0–10V).
16 | Commissioning 9.2 Protecting the motor Note: In fans equipped with an EC motor, there is no additional motor protection needed. The motor protection is integrated in the electronics of the motor. Damage to motor due to overcurrent, overload or short circiut. ♦ Lead-out temperature monitors must be integrated in the control circuit in such a way that, if a fault occurs, the motor cannot switch on again automatically after it has cooled down.
Operation | Commissioning of speed-controlled fans Check the fan for vibrations at all normal operation speeds during commissioning. Determine and evaluate vibrations on the housing and bearing areas in accordance with DIN ISO 14694 depending on motor power and positioning. Measurable vibration velocities depend e.g.
18 | Troubleshooting/maintenance/repair Troubleshooting cont'd Air output of fan too low Grinding sounds when starting or operating the fan Thermal contacts/ resistors have triggered Motor does not rotate Electronics/motor overheated Impeller rotates in wrong direction. Change direction of rotation (swap two phases in case of a 3– phase motor). Wrong wiring configuration (e.g. Y instead of Delta). Check and possibly correct the wiring configuration. Pressure losses too high.
Troubleshooting/maintenance/repair | 12.2 Maintenance Warranty claims can only be made if maintenance work is carried out correctly and written evidence thereof is provided. We recommend regular maintenance intervals to ensure continuous fan operation. These maintenance intervals are specified in the “Activities” table below. In addition, the operator must carry out follow-up activities such as cleaning, replacing defective components or other corrective measures.
20 | Cleaning 13 Cleaning Safety information ♦ Observe 2 Important safety information, page 1 Procedure Keeping the fan clean extends its service life. • Install a filter monitor. • Change the filters of the ventilation system. • Do not use steel brushes or sharp-edged objects. • Do not use a high-pressure cleaner (steam jet cleaner) under any circumstances. • Do not bend the fan blades when cleaning.
Commissioning Report | □ □ Sinus filter □ □ Shielded cables □ □ Frequency converter Yes Motor protection No Motor protection switch or motor protection relay □ □ PTC resistor □ □ Thermal contact □ □ Electrical motor protection □ □ Resistance value [Ω]: Others: Yes Functional check No Impeller easily rotatable (by hand) □ □ Rotation direction acc.
Tel.: +49 (0)7930/9272-0 Fax: +49 (0)7930/9273-92 info@systemair.de www.systemair.de Roof fans · Installation and Operating Instructions · · en_GB · 2021-07-13 · 008 Systemair GmbH Seehöfer Str.