Installation, Operation and Maintenance instruction TFSR Roof fan AC/EC TFSK Roof fan AC/EC TOE Roof fan AC TOV Roof fan AC TFE Roof fan AC EN
Table of content 1 Introduction .......................................................... 1 1.1 Product description ...................................... 1 1.2 Intended use .............................................. 1 1.3 Document description................................... 1 1.4 Product overview......................................... 1 1.4.1 Product overview for TFSR fans .............................................. 1 1.4.2 Product overview for TFSK fans ......................................
1 Introduction 1.1 Product description The product is a roof fan with an EC motor or an AC motor, and a tilting mechanism for easy maintenance. The TFSK fans, TOE fans, TOV fans, and TFE fans are supplied with a square base plate. The TFSR fans are supplied with a circular base plate. The EC fans have an internal potentiometer for speed control during continuous operation. The internal potentiometer is installed on the terminal block from the factory.
1.4.2 Product overview for TFSK fans 4 3 2 5 1 6 7 2 1. Base plate 2. Service Lid 3. Fan impeller 4. Motor 5. Connection box 6. Name plate 7.
1.4.3 Product overview for TOE fans and TOV fans 1 2 5 6 3 4 7 1. Service lid with motor bracket 2. Fan impeller 3. Position of connection box and name plate with air flow direction arrow. The TOE fan is delivered with connection box, the TOV fan is delivered without. 4. Base plate 5. Casing 6. Screws attaching the lid to the casing 7.
1.4.4 Product overview for TFE fans 1 2 3 7 4 6 5 9 10 1. Name plate with airflow direction arrow 2. Mains isolator switch 3. Fan impeller and motor 4. Base plate 5. Duct connection 6. Lid lock 7. Motor bracket 8. Lid 9. Motor bracket screw 10. Screw for opening of lid 1.
1. Type designation: Product name, dimension and motor type. Refer to 1.5.1 Type designation 2. Input power, W 10. Serial number: part number/production number/production date 3. Frequency, Hz 11. IP class, enclosure class 4. Certifications 9. Weight, kg 12. Current, A 1 5. Scannable code 6. Find more information about the product on the Systemair documentation portal1 Note: 7. Country of production 8.
2.2 Safety instructions Warning Read the warning instructions that follow before you do work on the product. • Read this manual and make sure that you understand the instructions before you do work on the product. • Obey local conditions and laws. • The ventilation contractor and the operator are responsible for correct installation and intended use. • Keep this manual at the location of the product. • Do not install or operate the product if it is defective. • Do not remove or disconnect safety devices.
4 Installation 4.1 To do before the installation of the product 3 Attach the fan on to the roof curb with 4 screws. 4 Connect the primary electric supply to the connection box of the product. Refer to 12.3 Wiring diagrams. • Make sure that you have the necessary installation accessories: – Refer to 13 Accessory overview for an overview of the accessories.
3 Connect the primary electric supply to the connection box of the product. Refer to 12.3 Wiring diagrams. For the TFE fan, loosen the screws that hold the motor bracket to access the terminals that are attached to the motor bracket. 5 Electrical connection 5.1 To do before the electrical connection • Make sure that the electrical connection agrees with the product specification on the motor name plate. • Make sure that the environment for electrical connection is clean and dry.
5.5 Speed controller for EC motors 6 Commissioning Caution • EC motors are controlled through a stepless 0–10 V signal. • If strong vibrations occur during commissioning, immediately increase or decrease the fan speed until the vibrations are decreased. Continuous strong vibrations can cause damage to components. • Do not use power supply for the speed controller. • Refer to 12.3 Wiring diagrams and the instruction manual for the external speed controller. 5.
7 Operation Caution EC motors must be set to ON/OFF via the control input. To stop the product via mains supply decreases the life time of the motor. Systemair recommends to install external speed controller for easy access to control the input signal. 7.1 To start a product with an AC motor 1 Set the installed safety switch in the ON position. 2 Install the external speed controller. Refer to the instruction manual for the installed speed controller. 7.
Maintenance task Usual operation conditions Each 6 months Each year Unusual operation conditions. 1 Each 3 months Each 6 months Visually examine the product and its components for damage, corrosion and dirt. X X Examine the fan impeller for damage and imbalance. X X Clean the product and the ventilation system. X Do a check of all fasteners and make sure that they are fully tightened. Make sure that the product and its components are correctly operated.
9 Troubleshooting Note: If you cannot find a solution to your problem in this section, speak to Systemair technical support. Problem Cause Solution The fan impeller is not correctly balanced. Speak to Systemair technical support. There is dirt on the fan impeller. Clean the fan impeller carefully. Refer to 8.2 To clean the product. The fan impeller has damages or deformations because the transported air contains aggressive media. Speak to Systemair technical support.
Problem Cause Solution The fan impeller does not turn in the correct direction. Make sure that the electrical connection is correctly done. A phase loss occurred. If the motor is a 3-phase motor, make sure that no phase is missing. Note: This is not applicable for EC motors. The motor is overheated. Thermal contacts, PTC or resistors are released. • Do a check of the motor cooling impeller. • If it is possible, measure the resistance to do a check of the motor winding.
10 Disposal The product follows the WEEE directive. This symbol on the product or the packaging of the product shows that this product is not domestic waste. The product must be recycled at an approved disposal location for electrical and electronic equipment. 11 Warranty For warranty claims, send a written maintenance plan and the commissioning report to Systemair. The warranty is only applicable for these conditions: • The product is correctly installed and operated. • Motor protection is used.
12 Technical data 12.1 Technical data overview Max. temperature of transported air, °C Max. ambient temperature, °C Refer to the data sheet in the online catalogue at www.systemair.com. Sound pressure, dB IP class Voltage, current, frequency, enclosure class, weight Refer to the name plate. Refer to 1.5 Name plate for more information. Motor data 12.2 Refer to the motor name plate or the technical documentation from the motor manufacturer. Product dimensions 12.2.
12.2.2 Product dimensions for TFSK fans Note: If the unit of measure is not specified, the dimensions are given in millimetres.
H I A B C D J E K F G L M N A B C D E ØF G H ØI ØJ K L M N TOE /TOV 355–4 600 340 290 50 M8 (8x) 395 600 M20x1.5 12 (4x) 395 M8 (8x) 450 557 615 TOV 450– 4 800 400 350 50 M8 (8x) 487 800 M20x1.5 14 (4x) 487 M8 (8x) 590 757 830 12.2.4 Product dimensions for TFE fans Note: If the unit of measure is not specified, the dimensions are given in millimetres. E F B D C A G TFE 220 M A B C D E F G 421 209 36 421 421 209.5 209.
12.3 Wiring diagrams Abbreviation in wiring diagram Cable colour RD Red YE Yellow BU Blue WH White GN Green BN Brown BK Black GR Grey GY Green/Yellow 12.3.1 Wiring diagrams for AC fans TFSR fans TFSK fans TFSR 125 M TFSK 125 M TFSR 125 XL Sileo TFSK 125 XL Sileo TFSR 160 Sileo TFSK 160 Sileo TFSR 200 TFSK 200 TFSR 315 L**1 TFSK 315 L**1 TFSR 315 M** 1 TFSK 315 M**1 TFSR 315 Sileo TFSK 315 Sileo 1–phase 230 V 1.
TFE fans 1–phase 230 V TFE 200 M N L 12.3.2 GY BK BU BN C Wiring diagrams for EC fans Note: An internal potentiometer is installed on the terminal block from the factory. Remove the internal potentiometer when you use an external speed controller for the EC fan. N 12.3.
REE — Thyristor REE 1 and REE 2 - Surface mounting or with flush mounting casing included. REE 4 - Surface mounting. N Note: Starting currents must be considered when you select the speed controller type. Products that are used with this speed controller must have a built-in overheating protection and must be designed for thyristor speed control. N L (L) N N N L (L) N M M • L: the connection with cutting function on the speed control. • (L): the connection without cutting function.
A. Relay connection. There is always 230 V between ~ and N when the transformer knob is in one of the positions 1–5. B. Mains supply C. Earth D. Fan E. Thermostat F. Motor protection. If the motor protection is not in use, Tk must be looped together. FRQ5S-E-6A Frequency converter with built-in all-pole sine filter and 5-step switch.
RTRD A 3-phase transformer that controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted by using the control knob on the front of the unit. RTRD2-7 N L L RT RT FS FS TK TK A A B N L1 L2 L3 N L1 L2 L3 U V W A 230 V AC PE U W M 3~ E 01 V TB TB C A. If the function is not necessary, the terminals must be bridged B. Contact rating, 230 V AC/maximum 1 A C. OFF/ON D. OFF/ON (only by reset) 22 D E.
RTRDU Manual 5–step transformer with motor protection — a 3–phase transformer that controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted by using the control knob on the front of the unit. RTRDU A 0 B 0 5 15 4 24 3 1 1 2 3 2 3 N L L RT RT FS FS TB TB A A N L1 L2 L3 PE N L1 L2 L3 U V W A 230 V AC max. 1 A 230 V AC U F B 01 TB TB C D E A. If the function is not necessary, the terminals must be bridged B.
MTP 20 MTP 20 1/Vdc+ +10V 4/Vout 0...10V 2/Vdc- GND 3/Vout- EC-Basic EC-Basic 1/IN Vac 230V AC 2/IN Vac +10V 4/Out 0...10V 5/GND GND MTV–1/10 MTV 1/010 1/IN Vac 230V AC 2/IN Vac +10V 4/Out+ 0...10V 5/Out- GND S-5EC/FRQ MTP 10 10V +10V GND 0...10V A GND EC-Vent EC-Vent IN/RPM optional IN/10V OUT/PWN GND 24 TACH +10V PWM 0...
12.3.5 Wiring diagrams for ON/OFF controls for EC motors CO2RT-R(-D) CO2RT-R-D Supply +10V Neutral 0...10V Common GND 24V AC Relay NO Relay NC Din1 IR24–P IR24-P 24V +10V Neutral 0...10V Common GND 24V AC or DC Relay NO Relay NC 12.3.6 Din1 Wiring diagrams for demand control for EC motors EC Basic EC Basic-T for temperature control EC Basic-CO2/T for temperature and CO2 control EC Basic-H for humidity control EC-Basic 1/IN Vac 230V AC 2/IN Vac +10V 4/Out 0...
EC-Vent Demand control for up to 5 external sensors, 2 fans, dampers, heaters and coolers. The EC vent system has 2 units. The control board (CB) and the room unit (RU). Connect the fan to the control board and remove the internal potentiometer. EC-Vent IN/RPM optional TACH IN/10V OUT/PWN +10V PWM 0...
Control Board (CB) I 5 (GND) 6 (0-10V) 7 G + DC MAX 24V I max 50mA H 2 (+24VDC) 3 (0-10V) 1 (GND) 1 (tach output) 2 (GND) 3 (PWM) 4 (+10VDC) N L F OUT3 OUT2 24V D A GND ALARM FAN 24V D A GND E OUT1 IN2 C B IN2 WY +0-10V Br + 24VDC GND A/D PT1000 24V GND A/D PT1000 24V GND A/D PT1000 24V DEBUG J K USB 24V D A GND MODBUS INTERNAL IN3 NC C NO GND +24VDC GND IN/10V OUT/PWM IN/RPM CMN NC NO D RU N out N in L out L in A A. Mains supply, 230 V 1~AC (10 A) B.
MM6-24/D output signal selector Compares signals from connected inputs and transfers the signal to the control output. 1 Input 1 0...10 V 2 Input 2 0...10 V 3 Input 3 0...10 V 4 Input 4 0...10 V 5 Input 5 0...10 V 6 Input 6 0...10 V 7 System neutral 8 24 V AC 9 Signal neutral 10 Signal neutral 11 Output minimum 0...10V 12 Output maximum 0...10V Mains supply PCA 1000D2 Pressure controller PCA 1000/6000D2 R i = 4 kΩ p PI V 1(+) 2( ) +US GND A GND + ∆p - + US 3 1 01 10...
13 Accessory overview 13.1 Accessory overview for TFSR fans Note: For more information about accessories, refer to www.systemair.com or speak to Systemair technical support. 1 2 1. Fan 2. TOB: Roof curb with curbed covering plate 3. TOS: Roof curb with flat covering plate 13.2 3 Accessory overview for TFSK fans, TOE fans, TOV fans, and TFE fans Note: For more information about accessories, refer to www.systemair.com or speak to Systemair technical support.
1 4 3 2 6 5 30 1. Fan 2. FDS: Flat roof socket 3. FDS-L: Flat roof socket (large) 4. TG: Roof curb 5. STG: Connection plate – base plate 6.
14 EU Declaration of Conformity We, the manufacturer Manufacturer Systemair Sverige AB Address Industrivägen 3 739 30 Skinnskatteberg Sweden declare under our sole responsibility that the products Machine Roof fan Type/Model TFSR, TFSK, TOE, TOV, TFE fulfils the relevant provisions of following directives and standards Machinery Directive 2006/42/EC EN ISO 12100:2010 Safety of machinery – General principles for design - Risk assessment and risk reduction EN ISO 13857:2019 Safety of machinery – Saf
15 UK Declaration of Conformity We, the manufacturer Manufacturer Systemair Sverige AB Address Industrivägen 3 SE-73930 Skinskatteberg Sweden declare under our sole responsibility that the products Machine Roof fan Type/Model TFSR, TFSK, TOE, TOV, TFE fulfils the relevant provisions of following directives and standards Supply of Machinery (Safety) Regulations 2008 EN ISO 12100:2010 Safety of machinery – General principles for design - Risk assessment and risk reduction EN ISO 13857:2019 Safety of
33
last page Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg +46 222 440 00 mailbox@systemair.com www.systemair.com © Copyright Systemair AB All rights reserved EOE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.