OPTIGO 10 USER MANUAL

Optigo OP10 user manual Chapter 3 Technical data 8
Chapter 3 Technical data
Supply voltage............. OP10-230: 230 V AC; +10 / -15%; OP10: 24 V AC; ±15%. 50/60 Hz
Internal consumption.........................................................................................................6 VA
Operation
Climatic conditions according to IEC 721-3-3 ........................................................ Class 3k5
Ambient temperature ................................................................................................. 0...50°C
Ambient humidity..............................................................................................Max 95% RH
Mechanical requirements according to IEC721-3-3 ..............................................Class 3M3
Vibration.......................................................... IEC60068-2-6, Test FC, vibration Sinusoidal
Shock................................................................................................IEC60068-2-27, Test Ea
Transport
Climatic conditions according to IEC 721-3-2 ........................................................ Class 2k3
Ambient temperature .............................................................................................. -20...70°C
Air humidity ......................................................................................................Max 95% RH
Mechanical requirements according to IEC721-3-2 ..............................................Class 2M2
Vibration.......................................................... IEC60068-2-6, Test FC, vibration Sinusoidal
Shock................................................................................................IEC60068-2-27, Test Ea
Free fall............................................................................................ IEC60068-2-27, Test Ed
Storage
Climatic conditions according to IEC 721-3-1 ........................................................ Class 1k3
Ambient temperature .............................................................................................. -20...70°C
Air humidity ......................................................................................................Max 95% RH
Terminals......................... Disconnectable, so-called lift type for cable cross-section 2.5 mm
2
Protection class................................................................................................................... IP00
Material casing ............................................................................................. Polycarbonate, PC
Colour
Cover ............................................................................................................................. Silver
Bottom part..............................................................................................................Dark gray
Weight ................................................................ OP10-230: 370g; OP10:215 g incl. terminals
Dimensions.....................................122 (7 modules) x 120 x 64 mm (WxHxD incl. terminals)
LVD, Low Voltage Directive
This product conforms with the requirements of European LVD standard EN61010-1.
EMC emissions an immunity standard
This product conforms with the requirements of European EMC standards CENELEC EN
61000-6-1 and EN 61000-6-3 and carries the CE mark
Inputs
AI........................................................................................................... Resolution: 10 bit A/D
AI1...................................................................................... PT1000-sensor, range 5…+80°C
AI2................................................................................... PT1000-sensor, range -30…+50°C
UI
AI....................................................................................................PT1000, range 0…+80°C
or DI ........................................................................................ Closing potential-free contact
A
GND
................................................................................................................Reference for AI
UI+ ..................................................................................................................Reference for UI
DI................................................................................................ Closing potential-free contact
DI+ ..................................................................................................................Reference for DI