Optigo OP10 user manual Chapter 10 Configuration 29
Chapter 10 Configuration
All the configuration menus lie in the 10-seconds level. This level is accessed from the Base
Display by clicking and holding the encoder knob for 10 seconds.
There are numerous configuration menus covering all available options and combinations.
In some cases, making a certain choice in one menu will mean that you will only see certain
other menus. For example, the menu for setting the damper minimum limit is only shown if
you have configured AO2 to be a damper control output.
Menus 1.0 – 5.0
In the first set of configuration menus you choose which of the five control modes you wish
to run. The displayed symbol and the first digit in the menu-number show which control
mode is at hand
Menus X.1
Output type (control modes 1, 2, 3 and 4)
(where X depends
on your choice of alternative above)
For control modes 1,2, 3 and 4 you can, instead of the 0 – 10 V analogue output, choose to
use two digital outputs to control a 3-point (increase/decrease) actuator. In this case DO1 will
always be increase (open valve) and DO2 decrease (close valve).
In controlmode 5 you can only have 0 – 10 V analogue output.
Menus X.2 Output signals (control modes 1, 2, 3)
Here you choose the combination of output signals.
If you in the preceding menu have chosen analogue 0…10 V outputs, they can be configured
to the following combinations: