RK & RKT Control Damper Handbook
/13 | RK & RKT Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions & Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Ordering Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Technical Parameters Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
/13 | RK & RKT Description RK and RKT are control dampers for rectangular ducts. They are available with blade tightness class 1 (RK) or 2 (RKT), tested according to EN 1751. They can be used as control dampers for air flow adjustment. RKT is also foreseen as a shut-off damper in case of lower tightness requirements. The dampers can be supplied in a manual version with adjustment handle or with preparation for attachment of an actuator. The maximum recommended duct pressure for operation is 1000 Pa.
/13 | RK & RKT Dimensions & Weights H+50 H < 1000 H RK-...-R, RKT-...-R 53 W 20 106 W+60 Dimensions of RK-WxH-R and RKT-WxH-R - manual version For sizes where W ≤ 1000 mm and H ≤ 900 mm W 20 W+60 Dimensions of RK-WxH-R and RKT-WxH-R - manual version For sizes where W > 1000 mm and H > 900 mm H+59 H ≥ 1000 H+9 RK-...-R, RKT-...
/13 | RK & RKT H < 1000 H 103 W 115 W+60 H+50 12 RK-...-S, RKT-...-S 53 106 Dimensions of RK-WxH-S and RKT-WxH-S - version with actuator preparation For sizes where W ≤ 1000 mm and H ≤ 900 mm H ≥ 1000 H+9 103 W 115 W+60 Dimensions of RK-WxH-S and RKT-WxH-S - version with actuator preparation For sizes where W > 1000 mm and H > 900 mm H+59 12 RK-...-S, RKT-...
/13 | RK & RKT Weights of the dampers
/13 | RK & RKT Ordering Codes Product type RK - Non-Tight Regulating Damper (tightness class 1) RKT - Tight Regulating Damper (tightness class 2) Nominal dimensions WxH - Width x Height Positioning R - Manual S - Actuator preparation Note: For positioning version “S” the actuator is not part of the delivery Example of the Ordering Code RKT-600x300-S Tight damper type, nominal dimensions 600 mm x 300 mm, with preparation for actuator.
/13 | RK & RKT Technical Parameters RK 2,0 2,0 RKT 20 Nm 20 Nm 1,5 16 Nm 1,0 15 Nm H (m) H (m) 1,5 12 Nm 0,5 1,0 8 Nm 3 Nm 0 0,5 10 Nm 0,5 1,0 W (m) 1,5 5 Nm 0 2,0 0,5 1,0 W (m) 1,5 2,0 Damper positioning torque Legend 25% ... 100% The position of the damper blades is represented in angular degrees. 0° is fully open position, 90° is fully closed positon.
/13 | RK & RKT RK-1000x1000-R RK-2000x2000-R Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 2500 Pa 5000 7500 l/s 35° 60 dB(A) 40 Pa 4000 8000 12000 55 dB(A) 25° 20 25° 10 40 dB(A) 35 dB(A) 0° 30 dB(A) 25 dB(A) 4000 8000 16000 20000 24000 0° 30 dB(A) 25 dB(A) m³/h 12000 15° 50 dB(A) 45 dB(A) 15° 40 dB(A) 35 dB(A) 10 28000 25000 50000 75000 RKT-200x200-R RKT-500x500-R Pressure drop & A-weighted sound power l
/13 | RK & RKT Installation RK, RKT is mounted into the ductwork by a standard flange. The fixing bolts, nuts, clips and gaskets shall be delivered by the installer. The damper cannot be installed carrying any mechanical loads from other structures.
/13 | RK & RKT Transport, Storage and Operation
/13 | RK & RKT Supplement Any deviations from the technical specifications contained on our website and the terms should be discussed with the manufacturer. We reserve the right to make any changes to the product without prior notice, provided that these changes do not affect the quality of the product and the required parameters. Current information on all products is available on design.systemair.com.
Systemair DESIGN • 2022-03-14 • Handbook_RK_RKT_en-GB • 90EBCB85-C9CE-4A7D-87FF-2DA388096525 • Original instructions