CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU
Table Of Contents
62 Chapter 6 Input Status Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentActual.Cor_AlaPt(5)
L
10037
Alarm
Points
P1 exchanger malfunction
VentActual.Cor_AlaPt(6)
L
10038
Alarm
Points
Filter guard 1
VentActual.Cor_AlaPt(7)
L
10039
Alarm
Points
Flow guard
VentActual.Cor_AlaPt(8)
L
10040
Alarm
Points
External frost guard
VentActual.Cor_AlaPt(9)
L
10041
Alarm
Points
Deicing pressure guard
VentActual.Cor_AlaPt(10)
L
10042
Alarm
Points
Fire alarm
VentActual.Cor_AlaPt(11)
L
10043
Alarm
Points
External switch
VentActual.Cor_AlaPt(12)
L
10044
Alarm
Points
External alarm
VentActual.Cor_AlaPt(13)
L
10045
Alarm
Points
Supply Air control error
VentActual.Cor_AlaPt(14)
L
10046
Alarm
Points
Humidity control error
VentActual.Cor_AlaPt(15)
L
10047
Alarm
Points
High supply air temp
VentActual.Cor_AlaPt(16)
L
10048
Alarm
Points
Low supply air temp
VentActual.Cor_AlaPt(17)
L
10049
Alarm
Points
Supply Air Fan max limit
VentActual.Cor_AlaPt(18)
L
10050
Alarm
Points
Supply Air Fan min limit
VentActual.Cor_AlaPt(19)
L
10051
Alarm
Points
High room temp
VentActual.Cor_AlaPt(20)
L
10052
Alarm
Points
Low room temp
VentActual.Cor_AlaPt(21)
L
10053
Alarm
Points
High extract air temp
VentActual.Cor_AlaPt(22)
L
10054
Alarm
Points
Low extract air temp
VentActual.Cor_AlaPt(23)
L
10055
Alarm
Points
Electric heating is overheated
VentActual.Cor_AlaPt(24)
L
10056
Alarm
Points
Frost risk
VentActual.Cor_AlaPt(25)
L
10057
Alarm
Points
Low frost guard temp