CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

60 Chapter 6 Input Status Register
Chapter 6 Input Status Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
TimePro.TimeGroupFanFullSpeed
L
10001
Actual/Set
point
Set if timechannel full speed is active
TimePro.TimeGroupFanHalfSpeed
L
10002
Actual/Set
point
Set if timechannel reduced speed is
active
TimePro.TimeGroupCor_ExtraTimeG
roup1
L
10003
Actual/Set
point
Set if timer output 1 is active
TimePro.TimeGroupCor_ExtraTimeG
roup2
L
10004
Actual/Set
point
Set if timer output 2 is active
TimePro.TimeGroupCor_ExtraTimeG
roup3
L
10005
Actual/Set
point
Set if timer output 3 is active
TimePro.TimeGroupCor_ExtraTimeG
roup4
L
10006
Actual/Set
point
Set if timer output 4 is active
TimePro.TimeGroupCor_ExtraTimeG
roup5
L
10007
Actual/Set
point
Set if timer output 5 is active
VentActual.Cor_ExtendedRunActive
Full
L
10008
Actual/Set
point
Set if extended operation full speed
VentActual.Cor_ExtendedRunActive
Half
L
10009
Actual/Set
point
Set if extended operation half speed
VentActual.Cor_NeedHeatActive
L
10010
Supply,
Extract and
Room
temperatur
es
Set if ongoing support heating
VentActual. Cor_NeedCoolActive
L
10011
Supply,
Extract and
Room
temperatur
es
Set if ongoing support cooling
VentActual.Cor_DemandCO2Active
L
10012
CO
2
Set if ongoing support CO
2
VentActual.Cor_DeIcingActive
L
10013
Extract air
temp/De-
icing
exchanger
Set if ongoing de-icing
QDig.DI1
L
10014
Digital
inputs
Value of DI1
QDig.DI2
L
10015
Digital
inputs
Value of DI2