58 Chapter 5 Holding Register
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_FilterG
uard2Limit_X2
R
40507
2000
Settings, Alarm limits
Alarm limit filter guard 2 X2 (m
3
/h)
VentSettings.Cor_FilterG
uard2Limit_Y2
R
40508
150
Settings, Alarm limits
Alarm limit filter guard 2 Y2 (Pa)
VentSettings.Cor_Neutral
Zone
R
40509
0
Settings, General
Neutral zone around supply setpoint
before heating and cooling
VentSettings.Cor_ExtraU
nitSaturationHumidityLi
mit
R
40510
85
Settings, General
The Extra unit can be used in
Saturation mode. When the room
humidity rises above the Saturation
Humidity level limit (setpoint, default =
85 %), the cooler will be controlled by
the extra unit instead.
VentSettings.Cor_ExtraU
nitSaturationHyst
R
40511
1
Settings, General
Extra unit saturation hysteresis level (%
of room humidity)
VentSettings.Cor_NightC
oolSAFOffset
R
40512
0
Settings, night
cooling
SAF setpoint offset if pressure/flow
controlled SAF when free cool active
VentSettings.Cor_NightC
oolEAFOffset
R
40513
0
Settings, night
cooling
EAF setpoint offset if pressure/flow
controlled EAF when free cool active
AlaData.AlaPt112_Delay
Value
I
40514
120 sec
Settings, Alarm
Delays
Alarm delay, motor control 1
malfunction
AlaData.AlaPt113_Delay
Value
I
40515
120 sec
Settings, Alarm
Delays
Alarm delay, motor control 2
malfunction
VentiOWA.Cor_iOWA_
VAVAutoMode
X
40516
2
Settings, General
VAV Control mode (0=Off, 1=Manual,
2=Auto)
VentiOWA.Cor_iOWA_
VAVManual
R
40517
0
Settings, General
Manual control of VAV control signal
(0…10 V)
VentSettings.Cor_ExchFr
ostProtFunc
X
40518
0
Frost protection
exchanger
Exchanger frost protection function
active, 0 = No, 1 = Yes
VentSettings.Cor_ExchFr
ostProtTemp
X
40519
1
Frost protection
exchanger
Exchanger frost protection temperature
input, 0 = Exhaust air temp, 1 =
Outdoor temp, 2 = Extra unit temp
VentSettings.Cor_ExchFr
ostProtReduceSAF
R
40520
0
Frost protection
exchanger
Reduce of SAF (%) in frost protection
VentSettings.Cor_ExchFr
ostProtReduceEAF
R
40521
0
Frost protection
exchanger
Reduce of EAF (%) in frost protection
VentSettings.Cor_ExchFr
ostProtOffTime
I
40522
480
Frost protection
exchanger
Min. time (sec) between frost
protection
VentSettings.Cor_ExchFr
ostProtRunTime
I
40523
1440
Frost protection
exchanger
Min. time (sec) in frost protection
VentSettings.Cor_ExchFr
ostProtSetP
R
40524
-3
Frost protection
exchanger
Temperature (°C) for start of frost
protection
VentSettings.Cor_FireSA
FSpeed
R
40525
-1
Settings, Fire mode
SAF speed in fire mode 0…100 %, -1 =
fan runs in normal speed conditions