CORRIGO E VENTILATION VARIABLES FOR EXOLINE AND MODBUS 3.6 MANU

Chapter 4 Input Register 25
Signal name
EXOL type
Modbus address
Default value
Function
Description
VentSettings.Cor_ExpDi(0)
X
30214
Digital inputs
Connected signal on DI1 Exp. Unit 1:
0=Not used
1=SAF-Ind
2=EAF-Ind
3=P1-Heating
4=P1-Exchanger
5=P1-Cooling
6=Filter guard
7=Fire alarm
8=Fire damper-ind
9=Ext run 1/1
10=Ext run ½
11=External alarm
12=External switch
13=Flow guard
14=Rot.sent.exch
15=De-icing
16=Frostprotection
17=Overheatprotection
18=Recirculation run
19=Change over
20=Filter guard 2
VentSettings.Cor_ExpDi(1)
X
30215
Digital inputs
Connected signal on DI2 Exp. Unit 1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(2)
X
30216
Digital inputs
Connected signal on DI3 Exp. Unit 1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(3)
X
30217
Digital inputs
Connected signal on DI4 Exp. Unit 1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(4)
X
30218
Digital inputs
Connected signal on DI5 Exp. Unit 1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(5)
X
30219
Digital inputs
Connected signal on DI6 Exp. Unit 1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(6)
X
30220
Digital inputs
Connected signal on DI7 Exp. Unit 1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(7)
X
30221
Digital inputs
Connected signal on DI8 Exp. Unit 1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(8)
X
30222
Digital inputs
Connected signal on UDI1 Exp. Unit
1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(9)
X
30223
Digital inputs
Connected signal on UDI2 Exp. Unit
1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(10)
X
30224
Digital inputs
Connected signal on UDI3 Exp. Unit
1:
(See signal list for DI1)
VentSettings.Cor_ExpDi(11)
X
30225
Digital inputs
Connected signal on UDI4 Exp. Unit
1:
(See signal list for DI1)