Circular Fire Dampers | 5 / 16
Fire Resistivity
Circular re dampers are certied according to EN 15650, tested according to EN 1366-2
and classied according to EN 13501.
IN ACCORDANCE WITH EN 15650, EACH FIRE DAMPER MUST BE INSTALLED ACCORDING TO THE INSTALLATION
INSTRUCTIONS PROVIDED BY THE MANUFACTURER!
Tab. 1: Permitted installation methods for circular re dampers based on re resistivity
Legend
Rigid/Flexible supporting construction, with tested underpressure (Pa)
Only rigid supporting construction, with tested underpressure (Pa)
Wet Installation
Dry Installation
Damper‘s horizontal blade axis orientation
Damper‘s vertical blade axis orientation
ve Vertical supporting construction (wall, horizontal duct)
ho Horizontal supporting construction (oor/ceiling, vertical duct)
Dimension
Range
(mm)
Certicate No.
Product
Type
Fire
Resistivity
Supporting
Construction
Installation - Tested at Underpressure (Pa)
Wet Dry
100 ≤ DN
≤ 200
1396 - CPD - 0050
PKI-C-EI60S
EI60
(ve ho i↔o) S
ve 300 -
ho 300 -
PKI-C-EI90S
and
PKI-C-EI120S
EI90
(ve ho i↔o) S
ve 300 300
ho 300 -
EI120
(ve ho i↔o) S
ve 300 300
ho 300 -
Allowed Blade Axis Orientation