Electrical Data - WQL/WQH/WQRC 20 to 45
Compressors - 400 V / 3 Ph / 50 Hz
Standard unit without pump option - 400 V / 3Ph / 50 Hz
Pump data - 400 V / 3 Ph / 50 Hz
Sizes
Nominal
PNOM-CPS
(kW)
Nominal
INOM-CPS
(A)
Maximum
PMAX-CPS
(kW)
Maximum
IMAX-CPS
(A)
ISTART-CPS
LRA (A)
PF
(NOM)
PFC*
20 4,6 9,3 8,3 15 101 0,71 > 0.90
25 5,8 12,1 10,0 18 128 0,68 > 0.90
30 6,7 14,2 11,6 22 139 0,68 > 0.90
35 7,4 13,5 13,1 25 118 0,79 > 0.90
40 8,5 15,5 14,8 31 140 0,79 > 0.90
45 10,1 21,4 17,0 34 174 0,68 > 0.90
Sizes
Nominal
power input
(kW)
Maximum
power input
(kW)
Nominal
current input
(A)
Maximum
current input
(A)
Start-up
current (A)
20 5 8 9 15 101
25 6 10 12 18 128
30 7 12 14 22 139
35 7 13 13 25 118
40 9 15 15 31 140
45 10 17 21 34 174
Sizes
1PSP/E 1PSP/C
P
MAX-PUMP
(kW)
IMAX-PUMP FLA
(A)
PMAX-PUMP
(kW)
IMAX-PUMP FLA
(A)
20 1.02 1.87 1.02 1.87
25 1.02 1.87 1.02 1.87
30 1.02 1.87 1.32 2.35
35 1.32 2.35 1.32 2.35
40 1.32 2.35 1.32 2.35
45 1.32 2.35 1.32 2.35
(*) Power factor correction capacitor option installed.
(*) Soft-starter option installed.